Specifications

14
For easier maintenance, operation, and improved ventilation, be sure to install the PL at least
50 mm [1.97 in.] away from adjacent structures and other equipment.
Be sure that the surrounding air temperature and the ambient humidity are within their
designated ranges. (Surrounding Air Temperature: 0
o
Cto 50
o
C (0
o
C to 40
o
C for the model
without Fan, T41 model), Ambient humidity: 10 %RH to 85%RH, Wet bulb temperature:
29°C or less.) When installing the PL on the panel of a cabinet or enclosure, “Ambient
operation temperature” indicates both the panel face and cabinet or enclosure’s internal
temperature.
Be sure that heat from surrounding equipment does not cause the PL to exceed its standard
operating temperature.
When installing the PL in a slanted panel, the panel face should not incline more than 30°.
The PL Series unit does not support longitudinal mounting.
Installing
1 Installation Requirements
50
[1.97]
50
[1.97]
50
[1.97]
Unit: mm
50
[1.97]
50
[1.97]
50
[1.97]
50
[1.97]
Panel
face
Cabinet
interior
30
[1.18]
30
[1.18]
100[3.94]
Unit: mm [in.]
30° or less