Specifications

PL-6930 / PL-7930 Series User Manual
2-12
2.3 Interface Specifications
This section describes the specifications of each interface of the PL Series unit.
2.3.1 Serial Interfaces (COM1/COM2/COM3/COM4)
This interface is used to connect an RS-232C (serial) cable. A D-sub 9pin plug connector is used.
*
1
Number 9 pin's [RI/+5V]changeover is good only for COM2 and COM3. The factory default setting is
[RI]. For COM1 and COM4, [RI] can be available.
Use #4-40 (UNC)
fixing clamps to fix the joint of the interspace.
The PL unit’s serial port is not isolated. When the host (PLC) unit is also not
isolated, be sure to connect the #5 SG (Signal Ground) terminal to reduce the risk
of damaging the RS-232C circuit.
Inside the PL unit, the SG (Signal Ground) and FG (Frame Ground) terminals are
connected.
If you connect an external device to the PL using the SG terminal, make sure that
no short-circuit loops are formed in the system design proceedings.
Pin
Arrangement
Pin No.
RS-232C
Signal Name Direction Meaning
1 CD Input Carrier Detect
2 RD(RXD) Input Receive Data
3 SD(TXD) Output Send Data
4 ER(DTR) Output Data Terminal Ready
5 SG(GND) - Signal Ground
6 DR(DSR) Input Data Set Ready
7 RS(RTS) Output Request to Send
8 CS(CTS) Input Send Available
9 CI(RI)/5V Input/Output
Called status display/+5V Output
(Switching available*
1
)
FG FG -
Frame Ground
(Common with SG)
The ground (GND) is a signal ground. Make sure to connect it with the other unit’s
SG (Signal Ground) pin.
The COM4 is not allowed to use when the communication procedure to the Touch
Panel is applied to a COM port connecting.
9
6
5
1