User manual

Chapter 2 – Specifications
LT Series User Manual2–14
Output Circuit (Type A2)
+ -
COM
Internal Circuit
Internal Circuit
OUT
0V
B2
A5
A20
A2
A1
OUT
DC 24V
External
Power
Supply
3.5 A
Quick
Break Fuse
Rated Voltage
DC 24V
Maximum Allowable Voltage
DC 26.4V
Input Method
Source/Sink Input
Rated Current
5 mA (24V)
Input Resistance
4.7 k
Operation Range
ON Voltage: 21V or more
OFF Voltage: 7V or less
Input Delay Time
OFF to ON: 10 ms or less
ON to OFF: 10 ms or less
Common Lines
1
Common Lines Allocation
16 points/1 common line
External Connection
40-pin connector (used with Output section)
Input Points
16
Input Signal Display
LED lights when each point turns ON (logical side)
Status Display
None
Isolation Method
Photocoupler Isolation
External Power Supply
For Signal: DC 24V
Input Specifications (Type A2)