Rated Voltage
Rated Voltage Range
Output Method
Maximum Load Voltage
Output Voltage Drop
Output Delay Time
Voltage Leakage (when OFF)
Type of Output
Common Lines
Common Design
External Connection
Output Protection Type
Internal Fuse
3.5 A , 125 V Chip Fuse (non-replaceable)
Surge Control Circuit
Output Points
Output Signal Display
Status Display
Isolation Method
External Power Supply
DC 24V
DC 24V ±10%
0.2 A/point 1.6 A/common
2.5V or less
Sink Output
OFF to ON: 2 ms or less
ON to OFF: 2 ms or less
0.4 mA or less
Transistor Output
1
16 points/1 common line
40-pin connector (also used for Input)
Output is unprotected
Photocoupler Isolation
DC 24V
Diode
16
LED lights when each point turns ON
(logical side)
None
Output Specifications (Type A1)