User manual
Chapter 1 – Introduction
LT Series User Manual1–2
Stand-alone 32 point I/O System (Type A1/Type A2)
The LT can independently control up to 32 external I/O units (DC 24V 16-point
Input/16-point Output).
I/O Units
Connecting Flex Network units to the LT unit allows you to use the LT to control
remote I/O.
Flex Network I/O units are connected to the LT via the Flex Network I/F unit,
which is equipped with 2 channels — CH1 and CH2. Through these channels, the
LT can send identical communication data. You can select either one of these
channels, or both, when sending communication data to the external I/O units.
Using a single channel enables you to send communication data to 31 I/O units via
one channel, and to 32 I/O units via the other channel. Therefore, using both
channels, the LT can communicate with a total of 63 Flex Network I/O units.
Flex Network System (Type B)
LT
There are five (5) LT series unit types: Type A1, Type A2, Type B, Type B+ and Type C.
1.2 System Design
1.2.1 System Design
Name Model Description
LT Type A1 GLC150-BG41-XY32SK-24V
LTC Type A1 GLC150-SC41-XY32SK-24V
LT Type A2 GLC150-BG41-XY32SC-24V
16-point Input Sink/Source and 16-point transistor
Output Source type
LT Type B GLC150-BG41-FLEX-24V Flex Network I/F
LT Type B+ GLC150-BG41-XY32KF-24V
LTC Type B+ GLC150-SC41-XY32KF-24V
LT Type C GLC150-BG41-RSFL-24V Flex Network I/F and SIO I/F
LT Series
16-point Input Sink/Source and 16-point transistor
Output Sink type
16-point Input Sink/Source and 16-point transistor
Output Sink, and Flex Network I/F type