Specifications
Specifications
Item
All equipment in these lists has been tested with GP-PRO/PBIII C-Package03 software.
(as of February 2004)
Important:
• When extending the Pt100 input wire, make sure that the three conductors have exactly the same
resistance and length. Do not route this wire near high-voltage, high-current, high-frequency
cables (such as those for inverters) or power cables. Also, do not bundle it with any of these
cables; place them in separate wiring ducts.
• Pt100 input uses three conductors to eliminate wiring resistance and provide consistently precise
measurement.
• When wiring external power to the Analog Input connector, connect 24V to No. 4 pin, and 0V to
No. 5 pin.
Important:
• Do not route thermocouple input wiring near high-voltage, high-current, high-frequency cables
(such as those for inverters) or power cables. Also, do not bundle it with any of these cables;
place them in separate wiring ducts.
• When extending the thermocouple input, use the specified (J type, K type) compensating lead
wire. Because long compensating lead wires are subject to noise, the length should be kept
as short as possible.
• Make sure the compensating lead wire is connected with the correct polarity. If the polarity is
reversed, temperature measurements will be incorrect.
• There is no insulation between thermocouple channels. Use insulated
(non-grounded) thermocouples.
• When wiring external power to the Analog Input connector, connect 24V to No. 4 pin, and 0V to
No. 5 pin.
*1 The indication vaires depending on the temperature controller functions.
*2 The value varies depending on the functional specification. Depending on the functional specification, the is omitted.
*3 Communication is possible via the LT Series internal memory regardless of the external controller (PC,Single-board controller,etc,),
*1 A connector terminal block is included with the unit, and is also available separately as a maintenance option.
*2
Applicable connector: Weidmuller BL3.5/6LH 6-terminal screw clamp. Max. connectable wire size: 1.6 mm (AWG#14)
*1 A connector terminal block is included with the unit, and is also available separately as a maintenance option.
*2
Applicable connector: Weidmuller BL3.5/6LH 6-terminal screw clamp. Max. connectable wire size: 1.6 mm (AWG#14)
*1
*1
*2
*3
*1
1
2
3
4
5
6
Pin Assignments*2
Pin No.
Terminal Name Condition
PT1 A
PT1 B
PT1 B
PT2 A
PT2 B
PT2 B
Pt100 Input Ch1
Pt100 Input Ch1
Pt100 Input Ch1
Pt100 Input Ch2
Pt100 Input Ch2
Pt100 Input Ch2
1
2
3
4
5
6
Pin Assignments*2
TC1+
TC1-
TC2+
TC2-
TC3+
TC3-
Thermocouple Input Ch1
Thermocouple Input Ch1
Thermocouple Input Ch2
Thermocouple Input Ch2
Thermocouple Input Ch3
Thermocouple Input Ch3
16
16
Pin No.
Terminal Name Condition
*1 Temperature conversion data is indicated as the measured value x10.
*2 Except for delay time, depending of the LT unit’s scan time.
*1 Temperature conversion data is indicated as the measured value x10.
*2 Except for delay time, depending of the LT unit’s scan time.
Subjected Resistance
Temperature Sensor
Pt100
Error Detection
Disconnect Processing
Wiring
Insulation Resistance
Additional Function
Input
Characteristics
Input Part –
Internal Part
Measurable
Temperature Range
Accuracy
External Wiring Length
Conversion Time
No. of Input Channels
Temp. Conversion Data
*1
Insulation
Channel –
Channel
Power for analog (DC24V) 1st side and 2nd side (AC500V)
Linearize pulses
Approx. 85ms x filter frequency (1 to 64) *2
No Insulated
2 Channels
Celsius: -50°C to +400°C Fahrenheit: -58 F to +752 F
Celsius: -500 to +4000 Fahrenheit: -580 to +7520
±1.0% (Full Scale)
Each Channel: 50m max.
Photocoupler Insulated
Temperature conversion data when exceeding measured
temperature range
Exceeding the upper limit: 32767 Exceeding the lower limit: -32768
3-wire method
Temperature conversion data is 32767
Celsius (°C) Fahrenheit (F)
Specifications
Item
Subjected Resistance
Temperature Sensor
Error Detection
Disconnect Processing
Insulation Resistance
Additional Function
Input
Characteristics
Input Part –
Internal Part
Measurable
Temperature Range
Accuracy
External Wiring Length
Conversion Time
Number of Input Channels
Temperature Convertion Data*1
Insulation
Channel –
Channel
Thermocouple (J/K Type)
Power for analog (DC24V) 1st side and 2nd side AC500V
Linearize
Temperature conversion data is 32767
Each Channel: 50m max. (by compensating conductors)
Approx. 170ms x filter frequency(1 to 64) *2
No Insulated
Celsius: -100°C to +700°C, Fahrenheit: -148 F to +1292 F
Celsius: -100°C to +1200°C, Fahrenheit: -148 F to +2192 F
3 Channels
±1.0% (Full Scale)
Photocoupler Insulatied
Temperature conversion data when exceeding measured
temperature range
Exceeding the upper limit: 32767 Exceeding the lower limit: -32768
Celsius (°C) Fahrenheit (F)
J Type
K Type
Celsius: -1000 to +7000, Fahrenheit: -1480 to +12920
Celsius: -1000 to +12000, Fahrenheit: -1480 to +21920
J Type
K Type
Manufacture
Series Name
Model
Manufacture
Series Name
Model
Manufacture
Series Name
Model
#1 MODBUS protocol supported. #2 RKC protocol supported.
Yokogawa
M&C
Yamatake
RKC
Instrument
OMRON
OMRON
Shimaden
Chino
Mitsubishi
Electric
Fuji
Electric
Toshiba
Schneider
Inverter
Yasukawa
Electric
Yasukawa
Electric
Matsushita
Electric
JT Enginnering
HITACHI
Industrial Equipment
Systems
Shinko
Technos
Fuji Electric
Toho Denshi
Shimaden
Fenwal Controls
of Japan
UT100
UT2000
UT3000
GREEN
SERIES
SDC
DMC
CB
SR-Mini
SR-Mini HG
SRX
REX-F
LE100
SRV
MA900
HA900
HA400
SA200
E5_N Digital
Temperature Controller
SR80
E5_N Digital
Temperature
Controller
C
FC
SR90
MR13
EM70
LT
JU
FREQROL-A500
FREQROL-A500L
FREQROL-E500
FREQROL-F500
FREQROL-F500L
FREQROL-S500
FVR-E11S
FVR-C11S
VF-S9
VF-nC1
VF-S11
MINAS-A
JE-70
MINAS-S
VF-A7
L300P
FREQROL-B, B3
FRENICS5000G11S
FRENICS5000P11S
Varispeed G7/F7
SJ300
VS mini V7/J7
SD16
FP93
FIR
GC
FCL
PC-900
PCD-33A
JCR-33A
JIR-301-M
Microcontroller-X
(PXR)
DCL-33A
TTM-004
TTM-X04
TTM-10L
TTM-00B
TTM-100B
TTM-110B
TTM-120
TTM-300
TTM-300B
TTM-1020
AL
SR253
TTM-110
JCD-33A
Modular, Dual Loop
Temperature controller
13
LT Series Built-in Interface Specifications and Connectable Controllers
14
LT Series Built-in Interface Specifications and Connectable Controllers