Specifications

*1
*1 The ON Duty error (20%) will be reduced if the Output frequency is low.
*2 The ON Duty (effective range) will be widened if the Output frequency is low.
SpecificationItem
Rated Voltage
DC 24V
ExternalPower Supply
Polarity
Isolation Method
Input Signal Display
Input Points
Common Line Allocation
Common Lines
Input Delay
Time
Input Derating
Rated Current
Input Method
Max. Allowable Voltage
Input Impedance
Operation
Range
For Signal: DC 24V
None
Photocoupler Isolation
LED lights when each point turns ON
(logical side)
16
8 points/1 common line
2
OFF to ON: 0.5 to 20ms or less*2
ON to OFF: 0.5 to 20ms or less*2
ON Voltage: DC19V or more
OFF Voltage: DC5V or less
Approx. 2.7k (IN0, IN2, IN4, IN6)
Approx. 4.7k (Other input)
9 mA (DC24V) (IN0, IN2, IN4, IN6)
5 mA (DC24V) (Other input)
Source/Sink input
DC 28.8V
*1
FunctionSignal NamePin No.
B18
COM0
A9
A18
B9
COM1
COM2
COM3
Input Common (For IN0 to IN7) (For CT0 to CT3)
Input Common (For IN8 to IN15)
Output Common (For OUT0 to OUT7)
(For PLS0 to PLS3, PWM0 to PWM3)
Output Common (For OUT8 to OUT15)
LC (Low Current) OUT0 to OUT7 HC (High Current) OUT8 to OUT15
Item
Rated Voltage
DC 24V
Isolation Method
Output Signal Display
Surge Control Circuit
Internal Fuse
Output Protection Type
Output Points
Common Design
Common Lines
Type of Output
Output Delay Time
Maximum Load Current
Output Method
Rated Voltage Range
Output Voltage Drop
Current Leakage (when OFF)
For signal: DC 24V
Photocoupler Isolation
Zener Diode (DC39V±1V)
LED lights when each point turns ON (logical side)
2A Chip Fuse (non-replaceable) 5A Chip Fuse (non-replaceable)
Output is unprotected
16 (8 points/1 common line)
1 each
8 points/1 common line
0.1 mA
or less
Transistor Output
OFF to ON: 0.5 ms
or less, ON to OFF: 0.5 ms or less
0.5V or less
Type H1 Sink Output
DC 20.4V to DC 28.8V
External Power Supply
Type H2 Source Output
0.2 A/point 0.8 A/common 0.5 A/point 2 A/common
Specifications
Item
Counter Input*
DC 24V (Open Collector)
Max. Count Frequency
Count Edge Assignment
Count Register
Counter Mode Switch
Upper/Lower Limit Setting
Preload/Prestrobe
Marker Input (Counter Value Clear)
Phase
Calculated Speed
(Rise and Fall time)
Minimum Pulse Width
(Pulse Input)
Counter Input Points
Input Voltage
Input Impedance
Available Not Available
16 bit Up/Down counter
Depending on software settings
Not available
Available
None IN3
10kpps
1 phase
90 degree phase differential–2
phase signal;1 phase+directional signal
2.7 k
CT0(IN0), CT1(IN2) are used as a pair
CT0: A Phase, CT1: B Phase
ON Voltage: DC19V or more / OFF Voltage: DC5V or less.
2-Phase (One point)
Single Phase (4 points)
CT0(IN0), CT1(IN2),
CT2(IN4), CT3(IN6)
Specification
Item
Output Points
PWM OutputPulse Output
Pulse Acceleration/
Deceleration Speed
Pulse Array Maximum
Output Frequency
ON Duty
Load Voltage
Output Method
Max. Output Frequency
Min. Load Current
50% +/-20% (at 5kHz)
*1
10% to -90% (at 2.5kHz)
*2
2.5kHz
5kHz
(Total number of used channels)
Available
PLS0 to PLS3 (OUT0 to OUT3)
defined by user
PWMO to PWM3 (OUT0 to OUT3)
defined by user
DC24V
1mA
4 Points
*1 Exceeding the LT unit’s input rated voltage may affect the input
ON voltage, input points, or ambient operating temperature;
the unit’s input terminals may be damaged due to excessive
heat.Use Input Derating within the range shown in the chart
below, to prevent unit malfunction.
*2 Digital filter can be set at intervals of 0.5ms.
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
OUT15
OUT14
OUT13
OUT12
OUT11
OUT10
OUT9
OUT8
COM3
OUT7
OUT6
OUT5
OUT4
OUT3 (PLS3, PWM3)
OUT2 (PLS2, PWM2)
OUT1 (PLS1, PWM1)
OUT0 (PLS0, PWM0)
COM2
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
B18
IN15
IN14
IN13
IN12
IN11
IN10
IN9
IN8
COM1
IN7
IN6 (CT3)
IN5
IN4 (CT2)
IN3
IN2 (CT1)
IN1
IN0 (CT0)
COM0
A1
B1
A18
B18
Pin Assignments
Pin No. Pin No.
Signal Name
Signal Name
Using GP-PRO/PB C-Package 03, you can set the standard DIO for use as high-speed counter input.
Refer to the Manual.
Parenthesized signal names ( ) indicate when Pulse output (PLS*), PWM output (PWM*), or Counter Input (CT*) are used.
B2L3.5/36LH 36 pole spring-clamp connector (Weidmuller) Wire size: 0.3mm to 1.0mm (AWG#18 to AWG#22)
The terminals for DIO power supply are located on the analog input/output connector.
50µs50µs
100µs
t=10 µs or less(10kpps)
t
t
* Select one from the types listed.
0
10
20
30
40
50
(°C)
Ambient Operating Temperature
Input ON Rate
(%)
100
DC 24.0V to DC 26.4V
50
0
DC 28.8V
Sink IN and Source IN/Sink OUT
Analog Input Circuit Analog output Circuit
Sink IN and Source IN/Source OUT
Specifications
Item
No. of Input Channels
2 Channels
Insulation
Input
Characteristics
Input Filter
Input Range
Resolution
Input
Impedance
At Voltage Setup
At Current Setup
At Voltage Setup
At Current Setup
At Voltage Setup
At Current Setup
Brightness
Linearity
Input Delay Time
Absolute Max. Input Voltage
Each channel - Internal: Insulated
Between each channel: No Insulated
Each channel - Analog Power: Insulated
100 k
250
Power Supply
12 Bit (0-4000 (0mA to 20mA),4095 max. (at 20.475mA))
0V to 10V (10.2375V max.) *1
0mA to 20mA (20.475mA max.) *1
12 Bit (0-4000 (0V to 10V),4095 max. (at 10.2375V))
±1.0% of full scale (0°C to 50°C)
±3 LSB max.
Scan time + (2ms Input Channels)
DC15V (Voltage)/ 60mA (Current)
Move average sampling time 2ms
DC24V External Power Supply
Input Voltage Input Current
Digital Output
4095
4000
20mA 20.475mA
0
Analog Input
Digital Output
Analog Input
10V 10.2375V
4095
4000
0
*1 Switching the Voltage Input or Current Input can be set separately, in each channel.
*1 Switching the Voltage Input or Current Input can be set separately, in each channel.
Important:
Use twisted-pair, shielded coaxial cable for analog input line(s) and be sure these lines are placed
in a separate duct from high-frequency, live lines such as high-voltage, high-power lines, inverters, etc.
Specifications
Item
No. of Output Channels
AD: 1 Channel
Output
Characteristics
Insulation
Power Supply
Output
Range
Resolution
At Voltage Setup
At Current Setup
External
Allowable Load
At Voltage Setup
At Current Setup
At Voltage Setup
At Current Setup
Brightness
±1.0% of full scale (0°C to 50°C)
10k or more
0mA to 20mA (20.475mA max.) *1
ADP: 2 Channels
ADT: 2 Channels
0V to 10V (10.2375V max.) *1
12 Bit (0 to 4000 (0V to 10V), 4095 max. (at 10.2375V))
12 Bit (0 to 4000 (0mA to 20mA), 4095 max. (at 20.475mA))
500 or less
DC24V External Power Supply
Each channel - Internal: Insulated
Between each channel: Non-insulated
Each Analog Power channel: Insulated
Output Current
Output Voltage
Analog Output
10.2375V
10V
0
Digital Input
4000 4095
Analog Output
0
Digital Input
4000 4095
20.475mA
20mA
*1 When the Current Input is selected, ground Al* and Al* JP. *2 Connect to the FG terminal in the main unit, or connect directly to frame ground (FG).
*3
Ground this wire when noise or other problems occur during unit operation.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Pin Assignments*2
Pin No.
Signal Name
Condition
*1 A connector terminal block is included with the unit,
and is also available separately as a maintenance option.
*2 Recommended Connector and Wire.
BL3.5/16LH 16 pole screw-clamp type connector (Weidmuller).
Terminal block screw fastening torque : 0.2 to 0.4N m.
Maximum wire size : 1.6mm(AGW#14),Applicable to UL1015 or UL1007
Wire strip length : 4.5 to 6.0 mm [0.18 in. to 0.24 in.]
*3 Ground this wire when noise or other problems occur during unit operation.
24V
0V
FE
24V
0V
AO2I
AO2V
AOG
AO1I
AO1V
AIG2
AI2 JP
AI2 +
AIG1
AI1 JP
AI1 +
DIO Power 24V
DIO Power 0V
Terminal for Function Ground
*3
Analog Power 24V
Analog Power 0V
Ch2 Analog Output (Current)
Ch2 Analog Output (Voltage)
Analog Output Ground
Ch1 Analog Output (Current)
Ch1 Analog Output (Voltage)
Analog Input Ground
Ch2 Analog Input
Ch2 Analog Input
Analog Input Ground
Ch1 Analog Input
Ch1 Analog Input
1
16
When setting Current Output
When setting Voltage Output
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Extemal Power
Supply DC24V
Extemal Power
Supply DC24V
Extemal Power
Supply DC24V
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Internal Circuit
Extemal Power
Supply DC24V
Extemal Power
Supply DC24V
Extemal Power
Supply DC24V
*1 Ground this wire when noise
or other problems occur
during unit operation.
*2 The dotted line circuit is used
for the Sink IN circuit.
*1 Ground this wire when noise
or other problems occur
during unit operation.
*2 The dotted line circuit is used
for the Source IN circuit.
When setting Current Input
When setting Voltage Input
*
1
*
2
Pin No. Pin No.
*
3
*
2
*
3
11
LT Series Built-in Interface Specifications
LT Series Built-in Interface Specifications
12