Specifications

0
10
20
30
40 55
50
(
°C
)
Ambient temperature
Input ON rate
(%)
100
DC 24.0V to DC 26.4V
50
0
DC 28.8V
*1 JIS B 3502, IEC61131-2 compliant
Intermittent vibration: 10 to 57Hz, 0.075mm;
57 to 150Hz, 9.8m/s
2
Continuous vibration: 10 to 57Hz, 0.035mm; 57 to 150Hz,
4.9m/s
2
Ten times (for 80 minutes each) in X, Y, and Z directions.
*2 With terminal block attached.
*3 Digital input is for detecting signals from mechanical switching devices such
as relay contacts, push buttons, switches, etc.
*1 JIS B 3502, IEC61131-2 compliant.
- With intermittent vibration: 10 to 57Hz 0.075mm, 57 to 150Hz 9.8m/s2
- With continuous vibration: 10 to 57Hz 0.035mm, 57 to 150Hz 4.9m/s2
Movement in X, Y, Z directions 10 times (for 80 minutes)
If this unit is used at a voltage that exceeds the rated
input voltage, a combination of factors, including the
input ON voltage, the number of input points, and
the ambient temperature may lead to malfunction
due to excessive heat in the input section. To
prevent this kind of malfunction, use the table at the
right to ensure that the input derating is within the
range shown.
•The FN-XY32SKS41 uses a spring-clamp type terminal block.
FN-XY32SKS41FN-X32TS41 FN-XY16SK41 FN-XY16SC41
DC24V
DC20.4V to DC28.8V
10ms or less (for DC24V power supply)
AC500V at 10mA for 1 minute (between power/Input and Output, and FG terminals)
Above 10M at DC500V (between
power/Input and Output, and FG terminals
)
0˚C to 55˚C
–25˚C to +70˚C
5% RH to 95% RH (non-condensing) wet bulb temperature: less than 39˚C
5% RH to 95% RH (non-condensing) wet bulb temperature: less than 39˚C
0.1mg/m
3
or less (non-conductive levels)
Free of corrosive gases
Noise voltage: 1000Vp-p, Pulse Duration: 1µs, Arise time: 1ns
Contact discharge of 6kV (IEC 61000-4-2 Level 3)
Using 35mm DIN rail or screws
Natural air circulation
110mm (4.33in) x 95mm (3.74in) x 57mm (2.24in)
135mm (5.31in) x 95mm (3.74in)
x 46mm (1.81in)
*
1
350g or less
IP20 *
2
DC24V
DC28.8V
32 points
(common for sink/
source types-dual use)
16 points
(common for sink/
source types-dual use)
32 points
(common for sink/source types-dual use)
Type 1 *
3
DC15V or more
DC5V or less
4.2k
1.5ms or less
1.5ms or less
––
DC24V
––
––
––
––
DC20.4V to DC28.8V
Model
Unit Rated Voltage
Allowable Voltage Range
Allowable Voltage Drop
Internal Power Consumption
Voltage Endurance
Insulation Resistance
Electrical
Environmental
Structural
Input/Output
InputOutput
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Air Purity (Dust)
Corrosive Gases
Pollution Degree 2Pollution Degree
Vibration Resistance
Noise Immunity (via noise simulator)
Electrostatic Discharge Immunity
Installation Method
Cooling Method
Weight
External Dimensions
(W) x (H) x (D)
Rating
Rated Input Voltage
Max. Input Voltage
No. of Input Points
Input Type
Input ON Voltage
Input OFF Voltage
Input Impedance
Input
Delay
Output
Delay time
Rated Output Voltage
(from V+ to V–)
Rated Output Voltage Range
(from V+ to V–)
Max. Load Voltage
Clamp Voltage
Current Leakage
OFF – ON
ON – OFF
OFF – ON
ON – OFF
0.1mA or less
1ms or less
1ms or less
2
41
Number of Occupied Nodes
2.5W or less 3.5W or less
IP20 (Without terminal block)
Output Points
16 points
(open drain
sink output)
32 points
(open drain
sink output)
16 points
(open drain
source output)
0.2A/point
(16 points/1 common, max. common current 1.6A)
Short-circuit Protection
––
none
DC1.5V or less
Voltage Drop (ON Voltage)
DC39V±1V
––
––
––
––
32-point
Sink/Source Input
16-point
Sink/Source Input,
16-point Sink
Transistor Output
16-point
Sink/Source Input,
16-point Transistor
Source Output
32-point
Sink/Source Input,
32-point Transistor
Sink Output
Model
Unit Rated Voltage
Allowable Voltage Range
Allowable Voltage Drop
Internal Power Consumption
Voltage Endurance
Insulation Resistance
Electrical
Environmental
Structural
Ambient Operating Temperature
Storage Temperature
Ambient Humidity
Storage Humidity
Dust
Atmosphere
Vibration Resistance
Noise Immunity (via noise simulator)
Electrostatic Discharge Immunity
Installation Method
Cooling Method
Weight
External Dimensions
Rating
0˚C to 55˚C
–25˚C to +70˚C
30% RH to 95% RH (non-condensing) Level RH-1
30% RH to 95% RH (non-condensing) Level RH-1
0.1mg/m
3
or less (non-conductive levels)
Free of corrosive gases
*
1
Noise voltage: 1000Vp-p, Pulse Duration:
1µs, Arise time: 1ns
Contact discharge of 6kV (IEC 61000-4-2 Level 3)
Using 35mm DIN rail or screws
Natural air circulation
Input/Output
Resolution
Output/Input Channels
Conversion Time
Input/Output
Range
Input/Output
Range Switch
Calibration Function
Accuracy
Insulation Method
Conversion Timing
Processing
(after conversion)
Number of Occupied Nodes
0.3% / FS(25˚C) 0.5% / FS(0˚C to 55˚C)
12bit
4 (fixed)
2ms or less
Depends on rotary switch settings
OFFSET, GAIN Setting
(Setting the upper limit)
––
0 to 5V (impedance 1M)
0 to 5V (impedance 1k)
1 to 5V (impedance 1M)
1 to 5V (impedance 1k)
0 to 10V (impedance 1M)
0 to 10V (impedance 1k)
-5 to 5V (impedance 1M)
-5 to 5V (impedance 1k)
-10 to 10V (impedance 1M)
-10 to 10V (impedance 1k)
0 to 20mA (impedance 200)
0 to 20mA (impedance 400)
4 to 20mA (impedance 200)
4 to 20mA (impedance 400)
Photocoupler insulation
(between input terminals and internal circuits)
Photocoupler insulation
(between output terminals and internal circuits)
Simple Average
Running Average
Exclude Max./Min.values
sample data values
Continual conversion of all channels
(not selectable)
4
DC24V
DC20.4V to DC28.8V
10ms or less (for DC24V power supply)
4.8W or less 7.2W or less
0.35kg [0.77lb] or less
W168mm [6.61in] x H50mm [1.96in] x D50mm [1.96in]
FN-AD04AH11
FN-DA04AH11
IP30
AC1500V 10mA 1 min. (between input/output and FG terminals)
AC500V 1 min. (between power supply 1st Level and 2nd Level)
DC500V at 10M or higher
(between charging and FG terminals)
4-channel
Analog Input Unit
4-channel
Analog Output Unit
20
19
LT Series Remote I/O (Flex Network)
LT Series Remote I/O (Flex Network)
See our Web site for LT Series system application examples.