Installation guide
6
Output Specifications
LT3201-A1-D24-K Output Circuit (Sink type)
• Since the output terminals are not electrically protected, an output line might be short-cir-
cuited or a connection fault might damage the LT unit. Please install an applicable fuse to pre-
vent an overload in the circuit, if necessary.
Output Terminal OUT0 to OUT3 OUT4 to OUT5
Rated Voltage DC24V
Rated Voltage Range DC20.4V to DC28.8V
Output Method
LT3201-A1-D24-K Sink Output
LT3201-A1-D24-C Source Output
Maximum Load Voltage 0.2A /point, 1.2A /common
Output Voltage Drop DC0.5V or less
Output Delay
Time
OFF to ON
5µs or less (With output
at DC24V, 200mA)
0.5ms or less (With
output at DC24V, 200mA)
ON to OFF
5µs or less (With output
at DC24V, 200mA)
0.5ms or less (With
output at DC24V, 200mA)
Voltage Leakage (when OFF) 0.1mA or less
Clamp Voltage 39V ± 1V
Type of Output Transistor Output
Common Lines 1
Common Design 6 points/1 common line
External Connection 22-pin connector (also used for Input)
Output Protection Type Output is unprotected
Internal Fuse 2.5A, 125V Chip fuse (not replaceable)
Surge Control Circuit Zener diode
Output Points 6
Output Signal Display No LED indicators
Status Display Element None
Isolation Method Photocoupler Isolation
External Power Supply For Signal: DC 24V
L
L
+24V B8
0V A8
Internal Circuit
OUT5 A11
Internal Circuit
Fuse
2.5A
+
-
DC 24V
External
Power
OUT4 B11
OUT3 A10
OUT2 B10
OUT1 A9
OUT0 B9
Dummy Resistor
*1
*1 (Example) The output
delay time (OFF to
ON) is 1.5µs where
the output current is
DC 24V, 50mA. Install
an external dummy
resistor to increase
the amount of current
when more
responsiveness is
required and the load
is light.