Installation guide

3
General Specifications
Electrical Specifications
Environmental Specifications
Power Supply
Input Voltage DC24V
Rated Voltage DC19.2 to 28.8V
Allowable
Voltage Drop
10ms (max.)
Power
Consumption
18W (max.)
In-Rush
Current
30A (max.)
Voltage Endurance AC1000V 20mA for 1minute (between charging and FG terminals)
Insulation Resistance DC500V 10M (min.) (between charging and FG terminals)
Physical
Surrounding Operating
Temperature
0 to +50°C
*1
*1 When using in an environment where the temperature becomes or exceeds 40°C for an extended
period of time, the screen contrast level may decrease from its original level of brightness.
Storage Temperature -20 to +60°C
Ambient Humidity
10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Storage Humidity
10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Dust 0.1mg/m
3
and below (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment