Hardware manual

LT-4201TM/4301TM Hardware Manual
37
Wiring to the DIO Terminal Block
Introduction
Wiring Rules and Recommendations (see page 33).
Screwdriver Required to Wire Terminal Blocks
Recommended type: 1891348-1 (Tyco Electronics AMP)
If ano
ther manufacturer is used, be sure the part
has the following dimensions:
z point depth: 1.5 mm (0.06 in.)
z point height: 2.4 mm (0.09 in.)
Point shape must be DIN5264A and meet standard DN EN
60900.
Also, the screwdriver tip must be flat, as indicated, to access th
e narrow hole of the
terminal block:
The terminal blocks are a spring clamp type.
Procedure
Use the follo
wing procedure to connect the wires
to the terminal blocks:
NOTE: To remove the wire, reinsert the screwdrive
r into the square-shaped hole
and when the wire’s spring clamp releases, pull out the wire.
(1)
Wire should be 0.20...0.81 mm
2
(AWG 24...18), with the end twisted. Applicable
wire style are UL1015 and UL1007.
CAUTION
EQUIPMENT DAMAGE
Be sure to remove the terminal blocks fro
m the equipment prior to wiring.
Failure to follow these instructions can result in injury or equipment damage.
Step Action
1 Insert the screwdriver into the square-shaped hole.
This will open the wire’s round-shaped hole.
2 Hold the screwdriver and insert the wire into the wire’s round-sh
aped hole.
3 Take out the screw
driver from the square-shaped hole.
The round-shaped hole will then close, and the wire will be held securely in place.