Installation guide

11
Tightening the screws with too much force
can damage the LT unit’s plastic case.
The necessary torque is 0.5Nm.
Be sure to insert installation fasteners
in the recessed portion of a installation
fasteners hole. If the fasteners are not
correctly attached, the LT unit may shift
or fall out of the panel.
3. Wiring to the DIO Connector
Be sure to remove the DIO Connector
from the LT unit prior to starting wiring. Fail-
ure to do so may cause an electric shock.
Items Required to Wire Connectors
Screwdriver
Recommended type: 1891348-1 <Tyco Elec-
tronics AMP.>
If another manufacturer is used, be sure the
part has the following dimensions:
point depth: 1.5mm [0.06in.]
point width: 2.4mm [0.09in.]
Point shape should be DIN5264A, and meet
Security Standard DN EN60900.
Also, the screwdriver’s tip should be flat as
indicated in order to access the narrow hole
of the connector:
DIO Cable Specifications
Connecting the DIO Cable
(1) Insert a flatShead screwdriver, at an angle,
into the tool insertion hole (square-shaped
hole) of the connector.
(2) When inserting the flathead screw driver,
be sure that it is perpendicular to the cen-
ter division wall.
Make the insertion distance of the flathead
screwdriver approximately 4 mm. Inserting
forcefully may break the inside of the con-
nector and will a cause of contact defect.
Also, do not turn the flathead screwdriver
while the tip is inside of the tool insertion
hole (square-shaped hole).
(3) The adjacent wire insertion hole (round-
shaped hole) will be in an open state.
With the flathead screwdriver still
inserted, insert the wire into the wire
insertion hole (round-shaped hole).
(4) Remove the flathead screwdriver from
the tool insertion hole (square-shaped
hole). The wire insertion hole (round-
shaped hole) will close and the wire will
be secured. In the case of wire removal,
remove the desired wire by inserting a
flathead screwdriver into the correspond-
ing tool insertion hole (square-shaped
hole) following procedures (1) and (2).
(5) Insert the wired DIO connector straight
into the DIO I/F of the LT unit.
Be sure to strip only the amount of
cover required. If too much cover is
removed, the end wires may short
against each other, or against an elec-
trode, which can create an electric
shock. If not enough cover is removed
the wire cannot carry a charge.
DIO Cable
Diameter
AWG24 to 18
UL1015 or UL1007
Conductor Type Stranded Wire
*1
*1 If the Conductor’s end (individual) wires are not
twisted correctly, the end wires may either short
against each other, or against an electrode.
Conductor
Length
Screwdriver Tip
Shape
7 mm
[0.28in]
Screwdriver
Wire
Wire insertion hole
(Round-shaped hole)
Tool insertion hole
(Square-shaped hole)