User`s manual

Chapter 6 - GP RUN and Errors
GP-477R/577R Series User's Manual 6-13
Reference
Note:
*1 For details about the T-File (trend graph) and A-File (alarm messages),
Tag Reference Manual
Reference
Overlapping addresses, other than the ones mentioned above, can also
cause the Illegal Address message.
E.g. When the starting address of the System Data Area is set to 100, and
the tag below is setup:
The N-tag is set to 32 bits, meaning it uses two word addresses. Since the first
address is 99, the second address must be 100. Address 100 is ineligible for
use since it has already been used for the System Data Area.
UNSUPPORTED TAG IN SCREEN DATA
This message appears when the GP currently in use does not support the
desired Tag. Be sure to only use Tags that are supported by the current GP.
For Tag details, Tag Reference Manual
Overlapping Addresses Table
Tag Name/ Part ID No. Word Address Tag Format
N1 99 BCD32
Note:
Error 1 Error 2 Meaning
0C1
191
All or part of the T-File or S-tag
address range overlap the addresses
of System Data Area.
192
193
0C2
194 All or part of the System Data Area
address, A-File, or S-tag address
range overlap the addresses setup in
a T-File.
195
196
0C3
197
All or part of the T-File, or the S-tag
or K-tag address range overlap the
address range set in an A-file.
198
199
0C9 19B
All or part of the T-File, or the S-tag
or K-tag address range overlap the
address range set in an A-file.
*1
*1
*1
*1