User`s manual

Chapter 5 - Initializing the GP
GP-477R/577R Series User's Manual
5-18
For example, when these 4 GP unitsbit 0, bit 2, bit 3, bit 5are con-
nected, 002D (h) is written here.
Be certain to setup this data before running.
Turn all bits not related to the GP OFF.
Verification List
This area responds to the correspondence from each connected GP. In the
Verification List, when the same bit numbers as the Connection List turn
ON, the corre spondence is accepted. The Station Numbers of the commu-
nicating GPs turn their corresponding PLC bit number ON.
If the correspondence between the GP and PLC is correct, the same value as
in the Connection List is written to the Verification List.
For example, the value 002D (h) in the Connection List, setup as the 0 bit, 2
bit, 3 bit, and 5 bit, writes to the Verification List.
When the Connection List and Verification List do not match,
a COMMUNICATION ERROR occurs. Check the setup again.
When changing the connection, first turn all the bits OFF.
Even if the GP is connected, if the Connection List is turned
OFF, data transfer cannot occur, and an error will not display.
STATION NO.
This is the setup for the GP Station Number mentioned in the above section.
The setup range is from 0 to 15, and the only other restriction is the GP
STATION NO. must be unique in the system. If STATION NO.'s are repeated, a
COMMUNICATION ERROR occurs.
The STATION NO. is the number allocated to the particular GP unit. This
number is not related to the Link Unit Machine number.
00000000
0000
00000000
0000
00000000
1
0
11
0
1
00
Bit 15
Bit 0
Note:
!!
!!
!
Important
!!
!!
!
Important
1111
1111
Connection List 002D (h)
Connection List
Verification List
002D (h)
002D (h)