User`s manual
Chapter 3 - Installation and Wiring
GP-477R/577R Series User's Manual 3-5
When the FG terminal is connected, be sure the wire is grounded. Not
grounding the GP unit will result in excess noise.
• Wherever possible, use thick wires (max 2mm
2
) for power terminals, and twist the
exposed wire ends when connecting the Ring Terminals.
• Please use the following sized Ring Terminals.
• To prevent the Ring Terminals from causing a short when the terminal block
attachment screws are loosened, be sure to use sleeve-type Ring Terminals.
• Do not wire the cable either near or parallel to high voltage or high current power
lines.
!!
!!
!
Important
Note:
3.2 Wiring Cautions
1. Connecting the GP's Power Cable
over Ø3.2mm
under Ø6.0mm
• To avoid an electric shock, be sure the GP’s power
cord is unplugged from the main power outlet
when connecting the power cord terminals to the
GP unit.
• The GP477R-EG41-24VP and GP577R-TC41-24VP
panels accept DC 24V power only. Using an incor-
rect power supply can damage both the power
supply and the GP.
• Be sure to connect a breaker type power switch to
the GP’s power cord.
• When connecting the power cord power terminals
to the GP, be sure to ground the FG (
) terminal,
since there is possibility of an electric shock if the
GP malfunctions.
WARNING
WARNING