User manual

Chapter 3 - Installation and Wiring
GP-2400/2500/2600 Series User Manual
3-2
Creating a Panel Cut
Create the correct sized opening required to install the GP, using the installation
dimensions given.
2.5.4 GP Panel Cut Dimensions
The installation gasket, installation brackets and attachment screws are all re-
quired when installing the GP.
Check that the installation panel or cabinet’s surface is flat, in good condition and has
no jagged edges. Also, if desired, metal reinforcing strips can be attached to the inside
of the panel, near the Panel Cut, to increase the panel’s strength.
For easier maintenance, operation, and improved ventilation, be sure
to install the GP at least 100 mm [3.94 in.] away from adjacent struc-
tures and other equipment.
Panel thickness should be from 1.6mm [0.06in.] to 10mm [0.4in.]. De-
cide the panel’s thickness based on the level of panel strength required.
Panel Cut
Area
Panel