SIMPLE TIPS FOR DEEP CYCLE BATTERY BANK SIZINING
In preparaon for baery sizing, know:
ELECTRICAL USAGE - the amount of energy consumed 1 day in Wa-
hours (Wh)
DAYS OF AUTONOMY - days of baery back-up required if unable to
charge the baeries by any means.
DEPTH OF DISCHARGE - limit of energy withdrawal to which you will
subject the deep cycle baery bank.
• Deeper discharge = Shortened baery life.
• Recommended: never discharge a deep cycle baery below 50% of
its capacity
• O-grid applicaons, a 25% DoD will extend baery life signicantly
TEMPERATURE - Standard for most baery rang is 25 ° C /(77 °F).
• Cold temperatures = reduced baery capacity
• High temperatures = shortened baery life
RECOMMENDATION - Keep the number of parallel strings of baeries to
three or fewer (one is preferred and considered best pracce). More than
three strings of baeries, risks shortening baery life due to uneven
charging.
Baeries in Series = Voltage is Addive
Baeries in Parallel = Ah is Addive
*Example: 2 12V 100Ah Baery Bank
Series 24V 100 Ah
Parallel 12V 200 Ah
• A system load of 6,000 Wa-hours per day
• 3 Days of Autonomy (back-up) needed
• Planned Depth of Discharge (DoD): 40%
• Baery bank ambient average low 15.6 °C (60 ° F)
CALCULATIONS: calculate baery bank size, use example below:
STEPS:
EXAMPLE:
3 days of Autonomy:
6,000 x 3 = 18,000 Wh