Service manual
1
GB
Indoor Units Capacity For 12000BTU
Capacity Model
12000BTU
AWM123HX
AWS121HX
Cooling Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at high speed
INDOOR ENTERING AIR DB/WB TEMPERATURE [
0
F]
OUTDOOR
ENTERING AIR DB
TEMPERATURE[
0
F]
DATA 72/59 75/63 81/66 84/70 90/73
14~68
(protection range)
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
77
TC 11616 12336 13104 13872 14640
SC 10421 10603 10845 11027 11269
PI 0.72 0.73 0.75 0.76 0.77
86
TC 11040 11808 12576 13296 14064
SC 10118 10361 10542 10785 10966
PI 0.81 0.82 0.83 0.85 0.86
95
TC 10464 11232 12000 12768 13536
SC 9876 10058 10300 10542 10724
PI 0.88 0.90 0.92 0.93 0.94
104
TC 9936 10704 11424 12192 12960
SC 9634 9815 10058 10239 10482
PI 0.97 0.98 0.99 1.01 1.02
115
TC 9264 10032 10752 11520 12288
SC 9270 9512 9694 9936 10118
PI 1.07 1.08 1.09 1.11 1.13