Specifications

Published in U.S.A. www.johnsoncontrols.com
LN Series Free Programmable LN-PRGxxx-12 Controllers Installation Instructions 24
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.
Outputs Number of Outputs: 12
Universal Output Characteristics: 0-10 VDC linear; digital 0 to12 VDC (on/off), PWM, or
floating (0 to 12 VDC), 0 to 20 mA (jumper configurable); software configurable
Built-in snubbing diode to protect against back EMF, for example when used with a 12 VDC
relay.
PWM control: adjustable period from 2 to 65 seconds
Floating control:
minimum plus on/off: 500 ms, adjustable drive time period
HOA: Hand-Off-Auto-Switch (when equipped)
Hand position potentiometer range: 0-12.5 VDC
60 mA maximum at 12 VDC (60
°C; 140°F)
Load Resistance: minimum resistance 200 ohms for 0 to 10 VDC and
0 to 12.5 VDC, maximum 500 ohm for 0 to 20 mA output
Auto reset fuse
60 mA at 60
°C (140°F), 100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/does analog converter
Wireless Receiver
1
Communication: EnOcean® Wireless standard
Number of Wireless Input
2
s: 28
Supported Wireless Receivers: LN-WMOD315-0 and LN-WMOD868-0
Telephone Cord Cable: Connector: 4P4C modular jack, Length: 6.5 ft (2 m)
Electromagnetic
Compatibility
CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and light-
industrial environments (pending).
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-
industrial environments (pending).
LN Series
Communicating Sensor
Communication: RS-485
Number of sensors per controller: up to 12, in daisy-chain configuration
Cable: Cat 5e, 8 conductor twisted pair
Connector: RJ-45
I/O Extension Modules
(LN-IOE 400 Series)
Communication: RS-485
Number of I/O Extension Modules per controller: up to 2, in daisy-chain configuration
Compliance United
States
UL Listed, File E107041, CCN PAZX,
Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7,
Under CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that the products are in compliance with the
essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
1. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more
than one wireless input from the controller.
2. Some wireless modules may use more than one wireless input from the controller.
LN-PRG6x0 Series (Part 3 of 3)