Install Guide
TECNOELETTRA s.r.l. via D.Vioni n.5 – 42016 S. Rocco - Guastalla (RE) Tel.+39.0522.832004 Fax.+39.0522.832012
mail: info@tecnoelettra.it web: www.tecnoelettra.it
Cod. Doc. AT206-origineel E 3 / 4
Power ON – first start up
Power ON – clock programming
“AUTOMATIC TEST”: programming (only if necessary)
1 ÷ 30gg.
Save
Exit
Save
Exit
1 ÷ 30min.
Save
Exit
00.00 ÷ 23.59
“AUTOMATIC TEST”: enabled and disabled (only if necessary)
Push AUT or verify
that the red led of
AUT button is
lighting.
Push TEST to enable the
function. The yellow led is
lighting: on display appear
“On” for 1sec:
the test is enabled
ENABLED
Push AUT or verify
that the red led of
AUT button is
lighting.
Push TEST to disabled the
function. The yellow led goes
off: on display appear “OFF” for
1sec:
the test is disabled
Setup
Description
Range
Default
U.01
Automatic test interval time
1 – 30gg
3 gg
U.02
Test duration
1 – 30 min
10 min
U.03
Test start time
00:00 – 23:59
10:00
Verify that the Emergency
button is released: if not,
rotate it in clockwise
direction to unlock it. (only
if available)
During the first start up, U11
code flashes as a reminder
to programming the clock
Push RESET button to
confirm the message, and
remove it from display
x 7
Hold 5s.
DESCRIPTION
Default set-up:
the test is done every 3 days (U01), start at
10:00 (U03) and lasts 10 minutes (U02).
Hold 5s.
+
-
Default
+ ore
+ min
+ h.
+ min.
+
-
Default
Default
END
WARNING!
To avoid mode of operation different from those described, it is absolutely not recommended
changing parameters U04, U08, U09, U10 without prior consultation with a service center.
……
..
When the automatic test parameters are set, you have to enable this, as follows:
DISABLED