GSW705V Product Card
Table Of Contents
GSW720V
Main Features
Frequency Hz 60
Voltage V 440
Power factor cos ϕ 0.8
Phase 3
Power Rating
Emergency Standby Power ESP kVA 783.60
Emergency Standby Power ESP kW 626.88
Prime power PRP kVA 714.00
Prime power PRP kW 571.20
Ratings definition (ISO-8528)
ESP - Emergency Standby Power:
It is the maximum power available during a variable electrical power sequence, under the stated
operating conditions, for which a generating set is capable of delivering in the event of a utility power
outage or under test conditions for up to 200 h of operation per year with the maintenance intervals
and procedures being carried out as prescribed by the manufacturers. The permissible average power
output over 24 h of operation shall not exceed 70 % of the ESP.
PRP - Prime Power:
It is defined as being the maximum power which a generating set is capable of delivering continuously
whilst supplying a variable electrical load when operated for an unlimited number of hours per year under
the agreed operating conditions with the maintenance intervals and procedures being carried out as
prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not
exceed 70 % of the prime power.