Product Card

MPP - Modular Parallel Panel
Mounted on the genset, complete with digital control unit InteliVision5 for monitoring,
control, protection and load sharing for both single and multiple gen-sets operating in
standby or parallel modes (up to 32 gen-sets in island).
CONTROL SECTION
ON/OFF selector switch
Emergency push button
Differential protection with internal switch
5A Battery charger.
Potentiometer for voltage adjustment (internal)
Alternator AVR (single plug wiring)
CONTROL UNIT InteliVision5 (5,7” Colour TFT display 320×240 pixels)
Majors Measures Available:
- Generating set: Voltage, Current, Frequency, Hours-counter
- Generating set Power: kVA, kW, kVAr, Cos φ, kWh, kVAh.
- Mains: Voltage, Current, Frequency, kW, kVAr, Cos φ.
- Engine: Speed (r.p.m.), Temperature, Oil Pressure
- Fuel level, Battery voltage
Comand and Others:
- Operation modes: OFF, AMF function, Single Parallel to mains Island application,
Single Parallel to Mains AMF application, Mulitple parallel genset Island application.
- Pushbuttons: start/stop, fault reset, up/down/page/enter selection.
- Acoustic alarm.
Protection:
- Engine protections: low fuel level, low oil pressure, high engine temperature.
- Genset protections: under/over voltage, overload, under/over frequency, starting
failure, under/over battery voltage
- Others: overcurrent, shortcircuit, reverse power, Earth fault
Extra Instrumentation (analogue)
- Fuel level meter
- Mechanical hour counter
POWER SECTION
It integrates 4 poles motorized moulded case circuit breaker suitably rated with
thermal and magnetic overloads
Large and robust busbar with cables passage opening from the bottom for easy
power cable connection.
Provided with safety switch to trip circuit breaker if operator open the power section
door to operate on the bus bar.
SOCKET SECTION
• Multi-pin connectors for paralle running
Two wires facility for remote start/stop
• Plug for auxiliary power supply
SUPPLEMENT - Only available when order :
Socket Kit Type  SPKB1
3P+N+T CEE 400V 125A n 1
3P+N+T 400V 63A n 1
3P+N+T CEE 400V 32A n 1
3P+N+T CEE 400V 16A n 1
2P+T CEE 230V 16A n 1
230V 16A SCHUKO n 1
Each socket with its own circuit breaker  ●
Common differential protection for three phase sockets  ●
Each single phase provided with earth fault protection  ●
Other Kit Socket combinations available