Product Card

Genset Equipment
Container 20 feet High Cube
High structural resistance
ISO lifting hooks
CSC SAFETY APPROVAL
Double seal gaskets
Roof access ladder – roof security anchorage points
Leak proof basement with double leak detection system
Double draining
Aspiration: available with standard aspiration or with sand trap filter (optional).
Internal canopy lighting system with manual switch for easy operation even with low
ambient light conditions.
Hot part and rotating part protection.
Coolin system
The cooling system includes n°2 electro-fans mounted on a common monobloc
support, main features of the system:
N°2 Electrical Motors Siemens with PTC thermal sensor and oversized shaft bearing
(2x30kW, 26KW certificated up to 55°C)
Double water circuit (LT and HT)
Fan profile optimized for greater efficiency
Metal water piping with draining valves
Thermal sensor on engine hot water outlet
Easy control (front doors) and refiling (from roof)
The cooling system fans speed can be controlled by inverter (optional)
Exaust System
Exhaust thermal insulation:
Each silencers is equipped of a double insulation to limit the increase of temperature
inside the container.
Insulated exhaust piping form engine exhaust manifold to exhaust silencer.
Flexible exhaust compensator (one for each engine)
Efficient roof fixed exhaust silencers – rectangular type – (one for each engine)
Rain flaps on container roof
Fuel system
Fuel tank integrated
Double wall
Metal (weld sealing certificated)
Leak detection system
External refiling cap under lockable panel
Quick fuel connectors for external fuel tank
Easy extraction from container without disassembly of other element
Water Separator Filter RACOR (n.1 common filter for two gensets)
Heavy-Duty air Filters Donalson (N.2 - One for each genset)
Battery 4 Optima battery 75Ah/12V/975A with manual battery switch.
Easy and Fast Service & Maintenance
TWINGEN designed for easy inspection, service and maintenance through inspection
doors and panels.
Each macro element is easily removable for extraordinary maintenance if needed:
Generators
Fuel tank
Cooling system
Control panel