Product Card
GQW1400V
1MWe TWINGEN in container 20’ HC
Pramac TWINGEN system designed and engineered to work in a wide variety of
applications where high power, modular and safe supply is needed.
Power Rating
Frequency Hz 50
Voltage V 400
Phases № 3
Standby power LTP kVA 1394
Standby power LTP kW 1114
Prime power PRP kVA 1252
Prime power PRP kW 1000
Dual Frequency Switch 50/60Hz √
Frequency Hz 60
Voltage V 480
Phase № 3
Standby power LTP kVA 1562
Standby power LTP kW 1250
Prime power PRP kVA 1436
Prime power PRP kW 1140
Ratings definition (According to standard ISO8528 1:2005)
PRP - Prime Power:
It is defined as being the maximum power which a generating set is capable of delivering continuously
whilst supplying a variable electrical load when operated for an unlimited number of hours per year under
the agreed operating conditions with the maintenance intervals and procedures being carried out as
prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not
exceed 70 % of the prime power.
LTP - Limited-Time running Power:
It is defined as the maximum power available, under the agreed operating conditions, for which the
generating set is capable of delivering for up to 500 h of operation per year (whose no more than 300 for
continuative use) with the maintenance intervals and procedures being carried out as prescribed by the
manufacturers. No overload capability is available.