Product Guide
62
All pictures shown in this document are for illustration purpose only. Actual product features may vary due to product enhancement without notice.
PRODUCT GUIDE
–
GPW
Series
8.5.11.6 B10 – ERDF – Bus Bar Arrangement
The option Bus Bar Arrangement allows to have different neutral scheme connections, Genset start with
GCB open and 3 led for voltage presence and phase rotation.
8.5.11.7 B10 – SBT – Switch Breaker Trip
The option SBT allows higher protection against direct contact.
When the generator is working in case of unexpected opening of the doors, the circuit breaker open and
the load is disconnected and an alarm is present in the control unit.
8.5.12 B10 – SOCKETS PANEL AND POWER LOCK OPTION
For more info regarding Sockets panel compatibilities and scope of supply, see 6.3 SOCKET PANEL BOX
and 11 ANNEX C – SOCKETS PANEL BOX.
Socket Panel Box dimension for A18 LxWxH [mm] 570x511x208.
Auxiliary Power Input Socket included as standard.
Mandatory include ETP supplement with SPBx.
8.5.12.1 B10 – PWL – POWERLOCK
PWL option consist in a Power Lock Box is a 3 phase high power-
connecting unit, used as a
termination point for power cables. The boxes include a number of safety features to prevent incorrect
connection and disconnection.
All power lock devices are ‘keyed’ to eliminate the possibility of connecting with the wrong line, and color
coded to suit international 3 phase standards.
PWL are directly protected by the main circuit breaker of the generator.
Current size
[A]
Number of
copper
bars
Section of copper
bars
[mm2]
Recommended cable size
[3Ph+N+PE]
[mm2]
100A
5
15x5
3x35 + 1x16 + 1x16
125A
3x50 + 1x25 + 1x25
160A
3x70 + 1x35 + 1x35
250A
5 x (20x5)
3x95 + 1x50 + 1x50
320/400A
5 x (20x10)
3x(2x70) + 1x70 + 1
x70
Compatibility:
All genset.
Incompatibility: None. Supplement under definition.
Available as: Supplement.
Compatibility:
All genset.
Incompatibility: ETB.
Available as: Supplement.
Compatibility:
Only with ACP.
Incompatibility: MPP(Included), MRS
Available as: Supplement.