Product Guide
61
All pictures shown in this document are for illustration purpose only. Actual product features may vary due to product enhancement without notice.
PRODUCT GUIDE
–
GPW
Series
Operating elements:
- 1- Power On LED “ON”, flashes in case of interruption of the connecting leads E/KE orL1/L2
- 2- Alarm LED “AL1”, lights when the value falls below the set response value Alarm 1 and
flashes
in case of interruption of the connecting leads E/KE or L1/L2
- 3- Alarm LED “AL2”, lights when the value falls below the set response value Alarm 2 and
flashes in case of interruption of the connecting leads E/KE or L1/L2
- 4- LC display
- 5- Test button “T”: to call up the self-test. Arrow up button: parameter change, to move up
in the menu
- 6- Reset button “R”: to delete stored insulation fault alarms parameter change, to move
down in the menu
- 7- “MENU” button: to call up the menu system. Enter button: to confirm parameter changes.
8.5.11.5 B10 – ADI - Adjustable Differential Protection
ADI is an adjustable differential protection external to the control board.
It is a residual current relay with external toroidal transformer, useful to detect leakage current. The advantage
of this type of differential protection is that is possible to set sensitivity and intervention time.
Type A (up to IDn=5 A)
Operating voltage 230-400 Vac +10% / -15%
Auxiliary supply frequency 50-60 Hz
Operating temperature -25….+70 °C
Sensitivity settings IDn 0.03-0.1-0.3-0.5-1-2-3-5-10-30 A
Tripping time settings Dt 0-0.06-0.2-0.3-0.5-1-2-3-5-10 s
Protection degree IP20
Standards IEC/EN 60947-2; IEC/EN 62020
Compatibility:
All genset.
Incompatibility: IMD.
Available as: Supplement.