User's Manual Part 3

Controller Web Pages OS-1933-E3-003
044-05243 Rev A 3-15
Rectifiers – Current
The DC current output of each rectifier module. Total DC consumption is the sum of the four rectifiers. Current
sharing technology allows for equal readings for each channel. The DC current is displayed in Amperes.
Rectifiers – Voltage Out –The DC voltage output sensed from each rectifier module. Voltage should be
~28.5Vdc.
Rectifiers – Temperature –The temperature of each rectifier module in degrees Celsius.
Fans – Speed –The RPM display of each of the systems fans. If the system only utilizes 2 fans the FT (front
top) and RT (rear top) positions are active. Maximum RPMs are >4000.
Status – Alarms
This page displays the current detailed alarm status of the system. The items displayed are not editable and
are for information only.
Figure 3-18 Status - Alarms page
The alarms page is organized in a top and bottom section. The top lists on 3 columns the detailed system
alarms related to common system components. The bottom section is divided into the 3 sectors and detail RF
performance issues. A PASS should be displayed for all parameters. A FAIL signifies an issue to be resolved.
This page should be displayed during every maintenance visit.
User
This page allows for modifications to system identification, password and serial number display.
Figure 3-19 User page