User's Manual
044-05298 Rev A 3-1
Chapter 3
Installation
Introduction
This chapter contains unpacking, inspection, installation instructions, and recommendations for installing the
PAF-19XX-EX-XXX MCPA Indoor System.
Site Survey
Powerwave recommends that a site survey be performed prior to equipment ordering or installation.
Performing a detailed site survey reduces or eliminates installation and turn-up delays. Pay particular
attention to AC or DC power availability, cooling needs, floor space, and RF/DC cabling/breaker
requirements. See Chapter 5 for system dimensions and weights.
Space Requirements
The PAF system requires the following floor space for clearance (W x D x H): 28.5 inches (724 mm) x 78.2
inches (1986 mm) x 38.5 inches (978 mm). To properly service the system, an additional 48 inches (1220
mm) is required in the front of the unit. To permit proper airflow, allow a minimum of 8.27 inches (210 mm)
behind the PAF.
Unpacking and Inspection
This equipment has been operated, tested and calibrated at the factory. Carefully open the containers and
remove the equipment. Retain all packing material that can be reassembled in the event that the unit must be
returned to the factory. Please perform the following steps:
❑ Visually inspect equipment for damage that may have occurred during shipment. If possible, in
the presence of the delivery person.
❑ Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extrane-
ous packing material in connectors.
If the equipment is damaged, file a claim with the carrier once the extent of any damage is assessed.
If the equipment must be returned to the factory, contact the factory for a Return Material Authorization (RMA)
as described in Chapter 4.
Electrical Service Recommendations
Proper AC line conditioning and surge suppression is necessary on the primary AC input to the +27 VDC
power source. Powerwave recommends that all electrical service be installed in accordance with the National
Electrical Code (NEC) and any applicable state or local codes.
Table 3-1 lists a sample of DC cable ratings.