User's Manual
2-2 044-05xxx Rev A
approximately 42 BTU per hour of heat. The G3L-929-135 amplifier is designed to operate within the
extended low temperature and high temperature environments defined in Table 1-1.
Table 2-1 describes the heat load (at 120 Watts typical) for a 3-sector (70%), 2-sector (80%), omni (90%),
and typical (100%) site. Perform a site survey to determine actual air conditioning needs.
Table 2-1. Averaged Heat Loading
Amplifier
Power
No. Of
Amplifiers
3-Sector (70%)
Averaged
BTU/hour
2-Sector (80%)
Averaged
BTU/hour
1-Sector (90%)
Averaged
BTU/hour
100%
Typical
135 4 6,956 7,924
135 3 5,217 5,565 5,943
135 2 3,478 3,710 3,806 3,962
135 1 1,739 1,855 1,903 1,981
2-4 Electrical Load
Table 2-2 lists the current consumption at 27 Vdc.
Table 2-2. Averaged DC Current Load
Amplifier
Power
No. Of
Amplifiers
3-Sector (70%)
Averaged Current
2-Sector (80%)
Averaged Current
1-Sector (90%)
Averaged Current
100%
Typical
135 4 88.8 A 106 A
135 3 66.6 A 72.6 A 79.5 A
135 2 44.4 A 48.4 A 50.2 A 53 A
135 1 22.2 A 24.2A 25.1 A 26.5 A