The controller also monitors the battery compartment temperature. The output bus voltage is adapted with
consideration to the temperature changes of the batteries. The compensation slope is user selectable as one of
three values: -36mV/°C (-20mV/°F), –60mV/°C (-33.3mV/°F), and between -10°C (14°F) and 60°C (140°F). The
factory setting is –36mV (-3mV/°C/cell). If the probe is not connected or fails to open, the output voltage falls back
to factory preset and an alarm is generated.
The LVD controller card switch settings are given in the table below.