5119 User's Guide
Installation
4
Powerware
®
5119 User’s Guide www.powerware.com
WARNING
ThisUPScontainsitsown energysource(batteries).The output receptaclesmay
carrylive voltage even whenthe UPSisnot connectedto an ACsupply.
Donot removeor unplugthe input cord whenthe UPSisturned on. This removes
the safetyground fromthe UPSand the equipment connected tothe UPS.
To reducethe riskof fireor electricshock, installthisUPSin atemperature and
humidity controlled, indoor environment,free of conductive contaminants.
Ambient temperature must not exceed 40 C(104 F).Donot operate nearwater
or excessive humidity (95% max).
The sum ofearth leakage current fromthe loadconnected tothe UPSmust not
exceed 1.5 mA.
Installing the UPS
The following steps explain how to install the UPS. Figure 3 on page 6
shows a typical installation only. See “UPS Rear Panels” on page 7 for
the rear panel of each model.
CAUTION
Asmallamount ofarcingmay occurwhenconnectingan externalbatteryto theUPS.
Insert thebatterycable into the UPS batteryconnector quicklyand firmly.
NOTE Donot makeunauthorized changes tothe UPS;otherwise,damage mayoccur
to your equipment andvoidyour warranty.
1. If the UPS has an external battery, connect it to the UPS as
shownin Figure 3 on page 6.
2. If you are installing power management software, connect your
computer to the UPS communication port using the supplied
communicationcable.
Some powermanagement software has a Load Segment feature
that allows you to control UPS output receptacles. If you plan
to use this feature, read the appropriate sections of your power
management software manual before you install the UPS.