User's Guide Power Supply 9170
43
Powerware
®
9170 User's Guide LTM-1344 B Uncontrolled Copy
C H A P T E R 5
ISOLATED OUTPUT WIRING DIAGRAMS
The wiring diagrams in this section are unique and specific to
installations in which the output of the Powerware 9170 UPS is
galvanically isolated from the input.
Figure 37 through Figure 40 describe output wiring configurations for
various output voltages. Use Table 6 to find the desired wiring diagrams
and connect the output AC wiring to the proper Powerware 9170 system
power terminals. You must also set the operating menu parameter 7-3-4
for the required output voltage as shown in the wiring configuration
drawings.
NOTE For isolated outputs, all power modules in the Powerware 9170 UPS cabinet
must be split-phase modules, which have blue labels.
NOTE In isolated-output installations, connect the UPS green and yellow
neutral-to-ground wire (N-G bond) to UPS output terminal as illustrated in Figure 36 on
page 45.
Table 6. Wiring Diagrams for Isolated Output
UPS In
p
ut UPS Out
p
ut
Output Wires
External
Wiring Diagrams
UPS
Input
Voltage
UPS
Output
Voltage
Output Wires
External
Bypass
Input Output System
100/200
110/220
115/230
100/200
110/220
115/230
L1 L2 N*
Yes Figure 25a Figure 34 Figure 37
115/230
120/240
120/208**
115/230
120/240
120/240
L1, L2, N*
No
Figure 25a Figure 34 Figure 38
120/208** 120/208
L1 L2 N*
Yes Figure 25a Figure 35 Figure 39
120/208
127/220**
120/208
127/220
L1, L2, N*
No
Figure 25a Figure 35 Figure 40
*Split-phase power modules required.
**External bypass switch, if installed, must be Break-Before-Make.