User's Guide Power Supply 9170

Electrical Installation
38
Powerware
®
9170 User's Guide LTM-1344 B Uncontrolled Copy
System Wiring Diagrams
The following notes are referenced in the non-isolated system wiring
diagrams (Figure 28 through Figure 33). To determine which diagram is
correct for your site, see Table 5 on page 35.
NOTE 1 The customer must provide input overcurrent protection as stated in NEC
Section 240-21 or local codes. Size the protection device according to local code
requirements (see Table 1 on page 26).
NOTE 2 The UPS bypass switch must be installed within sight of the UPS. To properly
install, complete the voltage and phase check procedure in Startup for Hardwired
Units" on page 53. The wires coming from the side of the switch must be connected as
described in Step 10 on page 33.
NOTE 3 All AC circuit conductors, including the neutral and equipment grounding
conductors, must be the same size (ampacity), have the same rating (75°C) copper
wire, and be sized according to the input circuit breaker. The UPS input and output
conductors must be run through separate conduits.
NOTE 4 The customer must provide output overcurrent protection. See NEC
Section 240-21 or local requirements. See Table 13 on page 78 for maximum
output overcurrent protection device ratings.
NOTE 5 See Equipment Clearances" on page 7 for installation and service
clearances before installing the UPS. Use flexible conduit on the UPS or the external
battery cabinet if either must be moved.
NOTE 6 External UPS battery cabinets are optional. See Battery Cabinet Installation"
on page 17 for installation instructions.
NOTE 7 UPS output circuits shall be installed in dedicated conduit systems and not
shared with other electrical circuits.