Powerware ® 9135 Two−in−One UPS 5000/6000 VA User’s Guide
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: EN 62040−1−1 and EN 62040−2; IEC 60950−1 S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 2004/108/EEC, Council Directive relating to electromagnetic compatibility The EC Declaration of Conformity is available upon request for products with a
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK − Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR’S MANUAL − Refer to your operator’s manual for additional information, such as important operating and maintenance instructions. This symbol indicates that you should not discard the UPS or the UPS batteries in the trash.
Table of Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS Life Cycle Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Anticipate Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset or Disable LCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 56 56 Additional UPS Features . . . . . . . . .
Chapter 1 Introduction The Powerware® 9135 uninterruptible power system (UPS) protects your sensitive electronic equipment from the most common power problems including power failures, power sags, power surges, brownouts, line noise, high voltage spikes, frequency variations, switching transients, and harmonic distortion. Power outages can occur when you least expect it and power quality can be erratic.
INTRODUCTION Providing outstanding performance and reliability, the Powerware 9135’s unique benefits include: S Online UPS design with pure sine wave output. The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery. S Two−in−one form factor for using the UPS in a rack−mount configuration or as a standalone cabinet. S Hours of extended runtime with up to four EBMs per UPS.
Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. DANGER This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
SAFETY WARNINGS CAUTION S Batteries can present a risk of electrical shock or burn from high short−circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. S Proper disposal of batteries is required. Refer to your local codes for disposal requirements. S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
SAFETY WARNINGS S I overensstemmelse med internationale normer og bestemmelser for el−installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 3,5 milliampere. ADVARSEL S Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj kortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres af kvalificeret servicepersonale med kendskab til batterier og gældende forsigtighedsregler.
SAFETY WARNINGS S Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben. S Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet overschrijden.
SAFETY WARNINGS Tarkeita Turvaohjeita TÄRKEITÄ TURVAOHJEITA − SUOMI SÄILYTÄ NÄMÄ OHJEET Tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava UPS−virtalähteen ja akkujen asennuksen ja huollon yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohje myöhempää tarvetta varten. VAARA Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.
SAFETY WARNINGS Consignes de sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procédure d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter entièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuel afin de pouvoir vous y reporter ultérieurement. DANGER! Cet onduleur contient des TENSIONS MORTELLES.
SAFETY WARNINGS ATTENTION! S Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant d’un courant de court−circuit haute intensité. Observez les précautions appropriées. L’entretien doit être réalisé par du personnel qualifié connaissant bien les batteries et les précautions nécessaires. N’autorisez aucun personnel non qualifié à manipuler les batteries. S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité.
SAFETY WARNINGS S Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Geräten entfernt wird. S Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.
SAFETY WARNINGS AVVERTENZA S L’UPS contiene la propria fonte di energia (batterie). Le prese d’uscita dell’UPS possono essere sotto tensione anche quando l’UPS non è collegato all’alimentazione elettrica CA. S Nei modelli da 230 V è possibile che le prese d’uscita rimangano sotto tensione. Se la fonte di alimentazione in entrata dell’installazione è costituita da un collegamento linea−neutro (come accade nella maggior parte delle installazioni europee), la tensione delle prese d’uscita è pari a 0 V.
SAFETY WARNINGS Viktig Sikkerhetsinformasion VIKTIGE SIKKERHETSINSTRUKSJONER GJEM DISSE INSTRUKSJONENE Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og vedlikehold av UPS−enheten og batteriene. Les alle instruksjoner før utstyret tas i bruk, og gjem håndboken til fremtidig referanse. FARLIG Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres av AUTORISERT SERVICEPERSONALE.
SAFETY WARNINGS FORSIKTIG S Batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. høy kortsluttingsstrøm. Treff passende forholdsregler. Service bør utføres av kvalifisert servicepersonale med kjennskap til batterier og nødvendige forholdsregler. Hold uautorisert personale borte fra batteriene. S Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. S Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.
SAFETY WARNINGS S Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em umidade excessiva (máx: 95%). S Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 3,5 miliampères.
SAFETY WARNINGS ÏÐÅÄÓÏÐÅÆÄÅÍÈÅ S  äàííîì ÈÁÏ óñòàíîâëåíû ñîáñòâåííûå èñòî÷íèêè ýíåðãèè (áàòàðåè).  ÈÁÏ ìîæåò èìåòüñÿ íàïðÿæåíèå äàæå â òîì ñëó÷àå, åñëè îí íå ïîäêëþ÷åí ê ñåòè ïåðåìåííîãî òîêà. S Íà âûõîäíûõ ðîçåòêàõ ìîäåëåé ñ íàïðÿæåíèåì 230  ìîæåò áûòü íàïðÿæåíèå. Åñëè óñòðîéñòâî ðàññ÷èòàíî íà òèï ïîäêëþ÷åíèÿ ôàçà−íåéòðàëü" (êàê áîëüøèíñòâî óñòðîéñòâ, èçãîòàâëèâàåìûõ â Åâðîïå), íàïðÿæåíèå íà âûõîäíûõ ðîçåòêàõ ðàâíî 0 Â.
SAFETY WARNINGS Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalación y el mantenimiento del SIE y de las baterías. Por favor, lea todas las instrucciones antes de poner en funcionamiento el equipo y guarde este manual para referencia en el futuro. PELIGRO Este SIE contiene VOLTAJES MORTALES.
SAFETY WARNINGS PRECAUCIÓN S Las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por corriente alta de corto circuito. Adopte las precauciones debidas. Personal calificado de servicio que conozca de baterías y esté al tanto de las precauciones requeridas debe darle servicio al equipo. Mantenga al personal no autorizado alejado de las baterías. S Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes.
SAFETY WARNINGS S Minska risken för brand eller elektriska stötar genom att installera denna UPS−enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
Chapter 3 Installation This section explains: S Equipment inspection S UPS internal battery connection S UPS setup and installation, including Extended Battery Modules (EBMs) S Remote power−off (RPO) installation S UPS rear panels Inspecting the Equipment If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim for concealed damage.
INSTALLATION Checking the Accessory Kit NOTE Packaging must be destroyed according to waste management standards. Recycling icons are displayed for easy selection. Verify that the following additional items are included with the UPS: Table 1. UPS Accessory Kit Item Description UPS user’s guide or CD Screwdriver RS−232 serial cable Rackmounting kit for 19−inch (48 cm) bays Two sets of pedestals with screws for tower position Optional. Network Management Card EU models only.
INSTALLATION If you ordered an optional EBM, verify that the following items are included with the EBM: Table 2. EBM Accessory Items Item Description EBM user’s guide EBM cable EBM communication cable Rackmounting kit for 19−inch (48 cm) bays Pedestal extenders for tower position Joining bracket and screws for tower position EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
INSTALLATION Connecting the UPS Internal Battery To ensure proper battery operation: 1. Verify that the UPS is off and unplugged. 2. Remove the two screws from the battery switch (see Figure 2). Two Screws Battery Switch Figure 2. Removing the Battery Switch Screws 3. Slide the battery connector so that you can read Connected (see Figure 3). 4. Reinstall the two screws removed in Step 2. 5. Continue to the following section, UPS Setup." Figure 3.
INSTALLATION UPS Setup The Powerware 9135 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the UPS in a rack, continue to the following section, Rackmount Setup;" otherwise, continue to Tower Setup" on page 30.
INSTALLATION Installing the Rail Kit CAUTION S DO NOT install the UPS or EBM in a hermetically−closed environment without any exchange of air. S The UPS and EBM are heavy (see page 65): 1) Eaton strongly recommends to remove the battery tray from the UPS before lifting. 2) A minimum of two people are required to lift the cabinets into the rack. NOTE The rails and the necessary mounting hardware are supplied by Eaton. To install the rail kit: 1.
INSTALLATION 2. Recommended. Remove the UPS battery tray (see Figure 5): S Remove the UPS front cover (six screws). NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or disconnect it. S Place the front panel above the UPS. S Remove the two battery retaining brackets (four screws). S Slightly pull the battery tray, then lift it to extract it. Figure 5. Removing the Battery Tray EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.
INSTALLATION 3. Place the Powerware cabinet on a flat, stable surface with the front of the cabinet facing you. NOTE You can adjust the position of the mounting brackets. 4. Align the mounting brackets with the screw holes on the side of the cabinet and secure with the supplied M4 6 mm flat−head screws. 5. If installing additional cabinets, repeat Steps 3 and 4 for each cabinet. Figure 6.
INSTALLATION 6. Loosen the assembly wing nuts on both rail assemblies and adjust the rail size for the depth of your rack (see Figure 7). 7. Select the proper holes in the rail for positioning the UPS in the desired location in the rack. 8. Using two M6 12 mm flat−head screws, attach the rail to the rear of the rack. 9. Secure the rail to the front of the rack with two M6 12 mm screws. 10. Repeat Steps 8 and 9 for the other rail. Figure 7.
INSTALLATION 11. Optional. Install the rear hold−down brackets (included with the rail kit) if you need to move the rack enclosure with the UPS already rack−mounted inside (see Figure 8). Figure 8. Installing the Rear Hold−Down Brackets 12. Slide the UPS and any optional EBMs into the rack. 13. Secure the front of the cabinet to the rack using two M6 12 mm round−head screws on each side (see Figure 9). Figure 9.
INSTALLATION 14. Optional. If you installed the rear hold−down brackets, secure the brackets to the rear rails using two screws for each bracket (see Figure 10). Figure 10. Securing the Rear Hold−Down Brackets 15. If you removed the UPS battery tray in Step 2, replace the battery tray and secure with the battery retaining brackets. Replace the UPS front cover. 16. Continue to Installing the UPS" on page 35. EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.
INSTALLATION Tower Setup CAUTION S DO NOT install the UPS or EBM in a hermetically−closed environment without any exchange of air. S The UPS and EBM are heavy (see page 65). A minimum of two people are required to lift the cabinets into the pedestals. The setup varies depending on the number of cabinets you are installing: 1. Assemble the UPS pedestals (see Figure 11). Figure 11. Assembling the UPS Pedestals 2. For one cabinet, the pedestals must be installed. Continue to Step 3.
INSTALLATION UPS Indicators 150 mm (6") 450 mm (17.7") Figure 12. Tower Position with One Cabinet 5. Continue to the following section, Installing the UPS." EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
INSTALLATION 6. Install pedestal extenders for each additional cabinet: For two cabinets, insert the extender into position 3 on the pedestal (see Figure 13). For three cabinets or more, insert the extender into position 4 on the pedestal (see Figure 14). 4 1 23 4 1 23 Figure 13. Extending the Pedestals for Two Cabinets 4 123 4 123 4 123 Figure 14. Extending the Pedestals for Three or More Cabinets 32 EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
INSTALLATION 7. Carefully position the cabinet upright with the UPS indicators at the top and place in the pedestals (see Figure 15). 8. Adjust the pedestals to the size of the UPS and secure the pedestals with the captive screws. Figure 15. Tower Position with Two Cabinets EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
INSTALLATION 9. Align each joining bracket with the adjacent cabinet screw holes and secure with the supplied screws (see Figure 16). NOTE Joining brackets are required for installations with two or more cabinets. Joining Bracket Figure 16. Installing the Joining Brackets 10. If installing additional EBMs, repeat Step 6 for each cabinet. 11. Continue to the following section, Installing the UPS." 34 EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
INSTALLATION Installing the UPS NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage may occur to your equipment and void your warranty. See UPS Rear Panels" on page 44 for the rear panel of each model. To install the UPS and optional EBMs: 1. If installing an optional EBM, continue to Step 2; otherwise, continue to Step 4. 2. Verify that the EBM battery circuit breaker is OFF. 3. Plug the EBM cable into the battery connector.
INSTALLATION 4. If you plan to install power management software, connect your computer to the USB port or RS−232 communication port. For RS−232, use only the serial cable supplied in the accessory kit. For more information about communication options, see page 57. SWITCHED GROUP 1 CAUTION: BATTERY DO NOT DISCONNECT CONNECTOR BATTERY CABLE 180Vdc UNDER LOAD RS−232 Communication Cable RS−232 CONTACTSBATT. NO. RPO RS−232 Communication Port Figure 18. Installing the RS−232 Serial Cable 36 5.
INSTALLATION RPO Installation Installation of the RPO function must be carried out in compliance with applicable regulations. The cable is not included. In order to fully de−energize devices and the Powerware 9135 with the RPO port, it is necessary to: S Use a two−position switch (normally−open or normally−closed contact and held more than one second). S Connect this RPO switch to a device that trips all breaker(s) located upstream(1) and downstream(2) the Powerware 9135 UPS.
INSTALLATION UPS Electrical Connections WARNING Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Risk of electrical shock. CAUTION S For UPS models with hardwired outputs, overcurrent protection for the output AC circuit(s) is to be provided by others. S For UPS models with hardwired outputs, suitably rated disconnect switches for the output AC circuit(s) are to be provided by others.
INSTALLATION Recommended Downstream Protection (EU Models Only) The indicated protection ensures discrimination for each output circuit downstream of the UPS. If these recommendations are not followed, protection discrimination is not achieved and may result in a potential power interruption to the connected devices.
INSTALLATION Connecting the Power Cables (EU Models) WARNING S Only qualified service personnel (such as a licensed electrician) shall perform the electrical connection. Risk of electrical shock. S Before carrying out any connection, check that the battery circuit breaker and upstream protection device (utility input) are OFF (O). S Use included insulated ferrules with stranded wires. 1. Remove the terminal block cover (two screws) with the supplied screwdriver (see Figure 21).
INSTALLATION Input Cable Output Cable Figure 22. Installing the Input and Output Cables (EU Models) 6. Replace the terminal block cover and tighten the cables. 7. Secure the terminal block cover with the two screws removed in Step 1. 8. Plug the equipment to be protected into the appropriate UPS output receptacles using the supplied cables (see page 61 for more information on load segments). See Figure 23. Connect any high−power devices to the 16A outlet. 9.
INSTALLATION Connecting the Power Cables (U Models) WARNING S Only qualified service personnel (such as a licensed electrician) shall perform the electrical connection. Risk of electrical shock. S Before carrying out any connection, check that the battery circuit breaker and upstream protection device (utility input) are OFF (O). S Use included insulated ferrules with stranded wires. Remove the terminal block cover (two screws) with the supplied screwdriver (see Figure 21). RS−23 2 BAT .O N .T RPO 1.
RS−232 BAT .O N .T RPO INSTALLATION T N: C E N IO O TID C U E S LN B AE TY A O C C N D O R D O TT LA A R B E D YV N R R O E TT dc0U A D B N N 8T 1C O C 24A 5 −20V~, 200 Input Terminal Output Terminal GND L2 (N) GND L2 (N) L1 L1 Figure 25. Installing the Input and Output Cables (U Models) 5. Replace the terminal block cover and tighten the cables. 6. Secure the terminal block cover with the two screws removed in Step 1. 7.
INSTALLATION UPS Rear Panels This section shows the rear panels of the Powerware 9135 models. SWITCHED GROUP 1 (2) Sets of 2 Programmable, 10A Receptacles (4) 10A Receptacles Output Terminal Block Input Terminal Block (2) 16A Receptacles 12A Thermal Switch 20A Thermal Switch 12A Thermal Switch Communication Bay Relay Port EBM RJ−11 Connector EBM Battery Connector BATTERY CAUTION: DO NOT DISCONNECT CONNECTOR 180VdcBATTERY CABLE UNDER LOAD USB Port RS−232 Port RS−232 CONTACTS BATT. NO.
INSTALLATION (4) L6−30 Receptacles 200−250V~,24A Output Terminal Block Input Cord with L6−30P EBM Battery Connector BATTERY DO NOT DISCONNECT CONNECTOR BATTERY CABLE 180VDdc UNDER LOAD CAUTION: Communication Bay USB Port Relay Port RPO Port RS−232 Port RS−232 BATT. NO. RPO EBM RJ−11 Connector Figure 28. 5000/6000 VA, U Models EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
INSTALLATION 46 EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
Chapter 4 Operation This section describes: S The control panel S Turning the UPS on and off S Starting the UPS on battery S Operating modes S Display functions Control Panel Functions The UPS has a four−button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 29). Bypass Indicator Alarm Indicator Battery Indicator Power Indicator esc Escape Up Down Enter On/Off Button Figure 29.
OPERATION Turning the UPS On To turn the UPS on: 1. Verify that the UPS internal battery connector is connected (see Figure 2 on page 22). 2. Set the upstream circuit breaker (not included) to the ON position. The equipment is powered by utility power, but not protected by the UPS. Batteries are recharging. An eight−hour recharge period is necessary to get full backup time. The and indicators illuminate. To change the factory-set defaults, see User Settings " on page 52. 3.
OPERATION Turning the UPS Off To shut down the UPS: 1. Press the button for approximately three seconds The UPS beeps once, and the load is no longer protected by the UPS. It is powered by utility power. If the UPS is set in frequency converter mode, the equipment will not be powered. If the utility power is out of tolerance, the UPS will generate a 10 ms output calibrated break. 2.
OPERATION Normal Mode During Normal mode, the indicator illuminates. The UPS monitors and charges the batteries as needed and provides power protection to your equipment. Eco Mode During Eco mode, the indicator illuminates. Eco mode reduces the consumption of electrical power. Under normal conditions (utility power available), the equipment is supplied in ECO mode.
OPERATION Bypass Mode The UPS transfers to Bypass mode when: S The utility power is out of tolerence S There is an overload condition S The button is pressed S There is a malfunction The and utility power. indicators illuminate and the equipment is powered by Display Functions Figure 31 shows the basic menu structure.
OPERATION Access to Measurements Press the button on the UPS front panel to access measurements for voltage, current, frequency, power output, and battery capacity. Access to UPS Setup To access the UPS Setup menu: 1. Scroll to the UPS Setup menu by pressing the 2. Press the button. button to get access. esc Figure 32. Access to UPS Setup The following tables display the options that can be changed by the user. Table 3.
OPERATION Table 4. Output Settings Function Factory Setting Options Comments Output Voltage EU Models: 230V U Models: 208V 200V / 208V / 220V / 240V / 250V Freq Converter Disable Enable Output Frequency EU Models: 50 Hz U Models: 60 Hz 60 Hz User selectable under frequency−converter mode Eco Mode Disable Enable See page 50 Slew Rate 1 Hz / sec 0.
OPERATION Table 6. Battery Settings Function Factory Setting Options Comments Auto Battery Test Everyweek No test / everyday / everyweek /everymonth Low Batt Warning 20% 0 to 100% 1% increment User Batt Settings UPS reads number of battery modules connected From 0 to 95 Ah 5 Ah increment Deep Disch Protect Yes No Protection against deep discharge. If disabled, the Eaton warranty will be void. Access to Maintenance To access the Maintenance menu: 1.
OPERATION The following table displays the maintenance options. Table 7.
OPERATION Anticipate Maintenance Automatic warnings appear when maintenance actions need to be planned: Table 8. LCM Warning Details LCM Warning Details Signification BATTERY CHECK RECOMMENDED Battery is approaching its reliability end of life. Risk to reduce dramatically backup time. Reset or Disable LCM In case of any LCM messages displayed: S For temporary reset: press the esc button for at least three seconds while in the Status and Alarm menu to temporarily cancel the alarm status.
Chapter 5 Additional UPS Features This section describes: S Communication ports S Network Management Card S Load segments (PowerShare) Communication Ports The Powerware 9135 provides three communication methods that can be used simultaneously: S RS−232 or USB communication. Compatible with most power management software applications. Note that both ports cannot be used at the same time.
ADDITIONAL UPS FEATURES USB Port The UPS can communicate with a USB−compliant computer using Powerware LanSafe® Power Management Software or other HID−compliant power management software compatible with Microsoft® Windows® 2000 and XP operating systems that support HID devices. NOTE The latest versions of the Powerware LanSafe Power Management Software and the USB firmware are available at www.powerware.com. To establish communication between the UPS and a computer: 1. The USB port is hot−pluggable.
ADDITIONAL UPS FEATURES Relay Port When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed. Output relays specifications: S Voltage: 48 Vdc maximum S Current: 2A maximum S Power: 62.5 VA, 30W Example: for 48 Vdc, Imax=625 mA Figure 36 identifies the cable pins and Table 9 describes the pin functions. 5 4 9 NC NO 3 2 8 7 1 6 NO NO NO Common NOTE Normally−open (NO) Normally−closed (NC) Figure 36. Communication Port Table 9.
ADDITIONAL UPS FEATURES Network Management Card (Optional) It is not necessary to shut down the UPS before installing a communication card. 1. Remove the slot cover secured by two screws. 2. Insert the communication card into the slot. 3. Secure the card with both screws. SWITCHED GROUP 1 CAUTION: BATTERY DO NOT DISCONNECT CONNECTOR BATTERY CABLE 180Vdc UNDER LOAD Communication Card (restricted access) RS−232 CONTACTS BATT. NO.RPO Figure 37.
ADDITIONAL UPS FEATURES EU Model Load Segments (PowerShare) Each EU model UPS has programmable outlets as shown in Figure 38. During a power outage, you can keep key pieces of equipment running while you turn off other equipment. It is preferable to connect the non−priority loads to the programmable receptacles, 1 and 2 . This feature allows you to save battery power. See your power management software manual for details (refer to www.powerware.com for the latest information).
ADDITIONAL UPS FEATURES 62 EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
Chapter 6 Maintenance This section describes replacing the power module and battery tray. Hot−Swapping the Power Module WARNING Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Risk of electrical shock. This operation can be performed without interrupting the equipment. 1. Remove the UPS front cover (six screws). See Figure 39. NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or disconnect it. 2.
MAINTENANCE Hot−Swapping the Battery Tray CAUTION S Batteries can present a risk of electrical shock or burn from high short−circuit current. Observe proper precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries. S Remove watches, rings, bracelets and all other metal objects from the hands and arms. S Use tools with an insulated handle.
Chapter 7 Specifications Table 10. Input and Output Specifications Power Levels (Rated at Nominal Inputs) Model Number PW9135G5000−XL3UHW PW9135G5000−XL3U 5000 VA, 3500W PW9135G6000−XL3UHW PW9135G6000−XL3U 6000 VA, 4200W PW9135G5000−XL3UEU 5000 VA, 3500W PW9135G6000−XL3UEU 6000 VA, 4200W Output on Battery Power AC Input Nominal Voltage Voltage Range1 208V 156–280V Frequency Range2 Voltage3 Frequency 208V 60 Hz 230V 50 Hz 40–70 Hz (± 0.
SPECIFICATIONS Table 12. Power Connections Model Input Connection Output Receptacles U Models 10 ft, L6−30P power cord (4) NEMA L6−30R EU Models Hardwired Hardwired with (8) 10A, IEC 320−C13; (2) 16A, IEC 320−C19 Table 13.
Chapter 8 Troubleshooting This section explains: S UPS alarms and conditions S Service and support Troubleshooting LED Press the esc button to stop the audible alarm. NOTE In case of "MULTIPLE FAULT", press the to further details. button and the button to get access NOTE In case of "LCM WARNING", see Life Cycle Monitoring" on page 55. esc Escape Up Down Enter Figure 41. Troubleshooting LED EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1 www.powerware.
TROUBLESHOOTING Troubleshooting Not Requiring Eaton Service esc Figure 42. Environment Fault Press the button to display the following details: Displayed Details Signification Correction NO BATTERY The battery is incorrectly connected. Check battery connections. I/O BAD CONNECTION Utility input is not connected to the correct terminals. Check AC wiring. NO POWER MODULE The power module is not inserted. Check power module connections (see page 63).
TROUBLESHOOTING Troubleshooting Requiring Eaton Service NOTE In case of multiple fault, press the further details. button and the button to get access to esc Escape Up Down Enter Figure 43. Troubleshooting LED Display Signification Correction POWER MODULE FAULT Internal power module fault detected. Use "Enter" button to display details. In Parallel: see the note below to start the other UPS alone. Call the Help Desk. Replace the power module (see page 63).
TROUBLESHOOTING Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
Chapter 9 Warranty Two−Year Limited Warranty (US and Canada) Powerware UPS Models: 3105, 9120, 9125, 9135, 9140, and FERRUPS® up to 3.1 kVA WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation company ( Company"). LIMITED WARRANTY: This limited warranty (this Warranty") applies only to the original End−User (the End−User") of any Powerware 3105, 9120, 9125, 9135, 9140, and FERRUPS up to 3.
WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by Company personnel or performed by an authori
WARRANTY COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End−User.
WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by Company personnel or performed by an authori
WARRANTY OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Company shall have no obligation under this Warranty.
WARRANTY WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End−User’s equipment does not include reimbursement for or restoration of any data loss.