Corporation Battery Charger User Manual
35
Po werware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
T
A
E
T
T
T
T
T
TT
E
EE
EE
A
A
A
A
A
Figure 21. Knockout Pattern for Remote Battery Disconnect
Table A. Remote Battery Disconnect Power Terminations
Termi nal Size of Pressure Termination Terminal Function
E4 (+)
1 --- # 8 --- 3 / 0
UPS Battery Contactor K2 (+)
E 5 ( --- )
1 --- # 8 --- 3 / 0
UPS Battery Contactor K2 (---)
Breaker (+)
1 --- # 4 --- 3 0 0 k c m i l
Battery Disconnect (+)
B r e a k e r ( --- )
1 --- # 4 --- 3 0 0 k c m i l
Battery Disconnect (---)
Breaker (jumper)
1 --- # 4 --- 3 0 0 k c m i l
Battery Disconnect (jumper)
Battery Cabinet (+)
See Table C (Appendix A)
Stand---alone battery cabinet (+)
Battery Cabinet (---)
See Table C (Appendix A)
S t a n d --- a l o n e b a t t e r y c a b i n e t ( --- )
Table B. Batte ry Cab inet Terminations
Battery Cabinet Size of Pressure Termination
Series 685 ( 1 ) # 2 --- 1 / 0 k c m i l [ Br e a k e r ( + ) & ( --- ) ]
Series 1085 ( 1 ) 3 / 0 --- 2 5 0 k c m i l [ B r e a k e r ( + ) & ( --- ) ]