Owner manual

EN
Servicingofbatteriesshouldbeperformedorsupervisedbypersonnelknowledgeableof
batteries and the required precautions.Keep unauthorized personnel away from
batteries.
Whenreplacingbatteries,replacewiththesametypeandnumberofthesealedleadacid
batteries.
Themaximumambienttemperatureratingis40°
C.
This pluggable type A equipment with battery already installed by the supplier is
operatorinstallableandmaybeoperatedbylaymen.
Duringtheinstallationofthisequipmentitshouldbeassuredthatthesumoftheleakage
currentsoftheUPSandtheconnectedloadsdoesnotexceed
3.5mA.
Attention, hazardous through electric shock. Also with disconnection of this unit from
the mains, hazardous voltage stillmay beaccessible through supply from battery.The
battery supply should be therefore disconnected in the plus and minus pole of the
batterywhenmaintenanceorserviceworkinsidetheUPS
isnecessary.
ThemainssocketoutletthatsuppliestheUPSshallbeinstalledneartheUPSandshallbe
easilyaccessible.
In case smoke is found coming out from the device, please cut off the power supply
quicklyandcontactthedistributor.
Donotkeeporusethis
productinanyofthefollowingenvironments:
o Anyareawithcombustiblegas,corrosivesubstanceorheavydust.
o Anyarea with extraordinarily high orlow temperature (above40˚C or below
0˚C)andhumidityofmorethan90%.
o Anyareaexposedtodirectsunshineornearany
heatingapparatus.
o Anyareawithseriousvibrations.
o Outdoor.
Intheeventthatthereisfireoccurringinthevicinity,pleaseusedrypowerextinguishers.
Theuseofliquidextinguishersmaygiverisetothedangerofelectricshock.
ThisproductcomplieswiththesafetyandenvironmentalregulationsinEU.
Ifthetimearisestothrowawayyourproduct,pleaserecycleallthecomponentspossible.Batteries
andrechargeablebatteriesarenottobedisposedinyourdomesticwaste!Pleaserecyclethemat
yourlocalrecyclingpoint.Togetherwecanhelptoprotecttheenvironment.