Routing of communication cables or data lines should be kept separate from the UPS input,
output, and external battery cables.
Use cable cross section and protective device specication
Model VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
Rectier Input L1, L2, L3, N,
Bypass Input L1, L2, L3, N,
min. conductor cross section[mm ] 10 16
max. possible cross section[mm ] 35 35
Rectier Input L1, L2, L3, N breaker (A)
80A 230VAC 100A 230VAC
Bypass Input L1, L2, L3, breaker (A)
80A 230VAC 100A 230VAC
Rectier Input fuse (A)
80A 250VAC 100A 250VAC
Bypass Input fuse
80A 250VAC 100A 250VAC
Output L1, L2, L3, N,
min. conductor cross section[mm ] 10 16
max. possible cross section[mm ] 35 35
External Battery Cabinet Positive
pole(+),Neutral pole,Negative pole (-),
min. conductor cross section[mm ] 16 25
max. possible cross section[mm ] 35 35
External Battery Cabinet Fuse (A) in
Positive pole(+),Neutral pole,
Negative pole (-),
120A 250VAC 150A 250VAC
External Battery Cabinet breaker
(A) in Positive pole(+),Neutral
pole,Negative pole (-),
120A 250VAC 150A 250VAC
Protective Earthing conductor [mm ] Max 35
60A 250V AC Clearance distances:>=1.4mm
Break time<=15s
Backfeed protection device
Torque for xing above terminals 2.8-3 Nm
Internal battery switch 125A 690VAC