3) Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-45°C
<95% <1000m
-15°C-50°C
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Maximum
Power
100%
95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity
Current
crest ratio
±1% 0.9 lag
Synchronized
50/60Hz±10%
in Line mode
(AC mode)
±0.1% of
normal
frequency in
Battery mode
THD<2%
Full load
(Linear
Load)/
<5% for
reference
non-linear
load
100%-110% load
transfers to Bypass
mode after 5
minutes
110%-130% load
transfers to Bypass
mode after 1
minutes
130%-150% load
transfers to Bypass
mode after 10
second
>150% load
transfers to Bypass
mode after 2 second
3:1