AIR REQUIREMENTS CONT’D
* Thermostat Rating: Lower Temperature – Old Style
Higher Temperature – New Style
* Combustion Air Temperature: The output of the engine will decrease about 1% for
every 10°F of air temperature above 77°F or 25°C.
IMPORTANT: Insulation and Sound Absorbing Material used inside of the generator compartment
Must Not reduce the specified airspace clearances or restrict the airflow around the generator. Such
reduction in airspace may lead to an overheating situation and reduced generator performance. Also be
sure the air inlet and outlet openings meet the specified requirements. Allow clearance inside the
generator compartment for easy access when routine maintenance is required.
WARNING: The generator compartment Must Be sealed to prevent hazardous fumes and vapors from
entering the vehicles other compartments and interior spaces. Plugging holes and sealing all seams will
greatly reduce this hazard.
WARNING: Drip Proofing! When installing a generator, the area directly beneath the generator end of
the unit must incorporate a non-flammable barrier. This barrier needs to be made of sufficient material
able to withstand and prevent molten metal, burning insulation, flaming or sparking particles from
contacting any flammable materials at the bottom of the compartment.
6
7KW
ENGINE SPEED IN RPM 1800
OUTPUT IN HORSEPOWER 10.5
ENGINE INLET WATER TEMP. N/A
THERMOSTAT RATING* 160°F – 180°F
THERMOSTAT FULL OPEN 203°F
ENGINE OUTLET WATER TEMP.MAX. 230°F
HIGH TEMP. SHUTDOWN SWITCH 230°F
HEAT REJECTION – BTU / MIN. 673
HEAT REJECTION – BTU / HR. 40,397
AIR FLOW – CU. FT. / MIN. 1296
ENGINE OIL TEMP. MAX. 268°F
COMBUSTION AIR TEMP. * N/A