1200 S - Se ries 1200 W SWITCHED MODE DC POWER SUP PLY
Fea tures :
• Very high re li abil ity, MTBF 500.000 hrs • No RFI prob lems, RFI fil ters in out put and in put
• Natural convection cooling • Build-in diode for redundant parallel operating
• High efficiency 89% • Analog programmable
• Under-voltage alarm contact • Short circuit protected
• Low output ripple, 7 mV rms • Low inrush current
Spec i fi ca tions :
• Input voltage : AC 198-264 V 48-62 Hz 8.2 Arms • Output voltage : Screwdriver adjustable with 10
fuse 15 A T, crest factor 2.2 turn potmeter at the rear side.
: AC 99-132 V 48-62 Hz 16.4 Arms Also programmable by 2-5 V
fuse 25 A T • Efficiency : 89% at 230 V AC input.
: DC contact factory • Temp. coeff. : 5.10
-5
per C
• Insulation • Stability : 3.10
-4
during 8 hrs under
Input / output : 3750 V rms (1min) constant conditions, after 1 hr
Input / case : 2500 V rms (1min) warm up.
Output / case : 500 V DC • Regulation
• Inrush current : Limited by 39 Ohm (shorted after startup) Load 0 - 100% : Better than 10 mV
• Line disortion : Kept low by large low frequency choke input Line 198 -264 V : Better than 5 mV
• Power factor : 0.72 at 230 V AC input and full load. • Ripple + noise (BW = 20 MHz) : Max. 7 mV rms, 20 mV pp
• Safety : EN 60950 / EN 61010 • Output imp. : Less than 0.05 Ohm up
SELV / PELV ( for 1200 S 24 only ) to100kHz
• EMC : EN 61204-3 Power Supply Standard • Recovery time : 0.3 milliseconds to recover within
: EN 61000-6-3 Emission (EN 55022B) 100 mV after 50 to 100% load
: EN 61000-6-2 Immunity step. Max deviation 300 mV.
• Hold-up time : 15 ms at 115 or 230 V AC input
• VDE0160 impulse test : Input with stands non periodic impulse and full load. 30 ms at half load.
2.3 Ûn 0.3 ms of VDE0160 class 1 • Series operation : Up to 500 V total Voltage.
• Redundant parallel Use R+ connection via build-in
• Parallel operation : For safe parallel operation put current operation Schottky diode to separate the
limit switch at 'LO' ( max.1100 W) outputs. put current limit at 'LO'
Do not use remote sensing.
Mod els Volt age Cur rent
1200 S 24 12 -15 V 60 A
24 V 50 A
30 V 40 A
Mod els Volt age Cur rent
1200 S 48 24 -30 V 30 A
48 V 25 A
60 V 20 A