The IntelliStation Jr. LFIS075VL* and LFIS100VL* are electronic water mixing valves providing
user-directed control and monitoring water distribution. They include an electronic Control Module
featuring a color touch screen digital display to select desired outlet water temperature, an electroni-
cally actuated valve that mixes hot and cold water, a quick response temperature sensor and check
valves. These electronic mixing valves monitor mixed outlet temperature. They also feature a user
programmable high temperature Sanitization mode to help limit water borne bacteria as part of a
user-directed and controlled thermal eradication protocol.
These electronic mixing valves supports building automation system (BAS) communication with
BACnet MSTP and Modbus protocol, allowing remote programing and data viewing.
Installation and adjustment of these electronic mixing valves are the responsibility of the owner and
installer and must be done by qualified personnel in accordance with the manufacturer’s instruc-
tions, and complying with all governmental requirements, building and construction codes and
standards. It is recommended to install LFIS075VL or LFIS100VL as part of an ASSE compliant water
distribution system, including mixing valves and/or temperature limiting devices at all point-of-use
fixtures (faucets, sinks, tubs, showers, etc.) that are approved to ASSE 1016, 1069, 1070 and 1071.
The owner and user of the LFIS075VL or LFIS100VL is responsible for selecting and installing the
product in an appropriate water distribution system, proper sizing, maintaining proper water quality/
condition, and deciding what temperature is safe and appropriate for the water distribution users
and facility.
IntelliStation Jr. Description and Specifications
*The wetted surface of this product contacted by consumable
water contains less than 0.25% of lead by weight.