Operating Temperature Regulators - Type WM 3-Way Water Mix Instruction Manual
4
CAUTION: Do not exceed maximum pressure differentials for given valve sizes. The maximum differential is the
pressure the valve has against it at shutoff. Too large a differential can cause valve chatter and/or prevent shutoff.
MAXIMUM WATER CAPACITIES
TEMPERING Applications - Maximum MIXED FLOW
Gallons Per Minute Liters per Second
Valve Available Sizing Pressure Differential --- PSI Valve Available Sizing Pressure Differential --- kPa
Size Cv 246810152025304050 Size 7 15 30 45 60 75 100 125 150 200 250 350
1/2" 4.2 5.9 8.4 10 12 13 16 19 21 23 27 30 1/2" 0.3 0.4 0.6 0.7 0.8 0.9 1 1.1 1.2 1.4 1.6 1.9
3/4" 7.2 10 14 18 20 23 28 32 36 39 46 51 3/4" 0.5 0.7 0.9 1.2 1.3 1.5 1.7 1.9 2.1 2.4 2.7 3.2
1" 12 17 24 29 34 38 46 54 60 66 76 85 1" 0.8 1.1 1.6 1.9 2.2 2.5 2.9 3.2 3.5 4.1 4.6 5.4
1-1/4" 20 28 40 49 57 63 77 89 100 110 126 141 1-1/4" 1.3 1.9 2.6 3.2 3.7 4.2 4.8 5.4 5.9 6.8 7.6 9
1-1/2" 25 35 50 61 71 79 97 112 125 137 158 177 1-1/2" 1.6 2.3 3.3 4 4.7 5.2 6 6.7 7.4 8.5 9.5 11
2" 39 55 78 96 110 123 151 174 195 214 247 276 2" 2.5 3.6 5.1 6.3 7.3 8.1 9.4 10 11 13 15 18
2-1/2" 77 109 154 189 218 243 298 344 385 422 – – 2-1/2" 4.9 7.2 10 12 14 16 18 21 23 26 – –
3" 120 170 240 294 339 379 465 537 600 657 – – 3" 7.6 11 16 19 22 25 29 32 35 41 – –
4" 145 205 290 355 410 459 562 648 725 794 – – 4" 9.2 13 19 23 27 30 35 39 43 49 – –
BYPASS Applications - FULL FLOW thru BOTTOM Port (Top Closed)
Gallons Per Minute Liters per Second
Valve Available Sizing Pressure Differential --- PSI Valve Available Sizing Pressure Differential --- kPa
Size Cv 246810152025304050 Size 7 15 30 45 60 75 100 125 150 200 250 350
1/2" 2.2 3.1 4.4 5.4 6.2 7 8.5 9.8 11 12 14 16 1/2" 0.1 0.2 0.3 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.8 1
3/4" 6 8.5 12 15 17 19 23 27 30 33 38 42 3/4" 0.4 0.6 0.8 1 1.1 1.2 1.4 1.6 1.8 2 2.3 2.7
1" 8.9 13 18 22 25 28 34 40 45 49 56 63 1" 0.6 0.8 1.2 1.4 1.7 1.9 2.1 2.4 2.6 3 3.4 4
1-1/4" 16 23 32 39 45 51 62 72 80 88 101 113 1-1/4" 1 1.5 2.1 2.6 3 3.3 3.8 4.3 4.7 5.4 6.1 7.2
1-1/2" 18 25 36 44 51 57 70 80 90 99 114 127 1-1/2" 1.1 1.7 2.4 2.9 3.3 3.7 4.3 4.8 5.3 6.1 6.8 8.1
2" 30 42 60 73 85 95 116 134 150 164 190 212 2" 1.9 2.8 3.9 4.8 5.6 6.2 7.2 8.1 8.8 10 11 13
2-1/2" 77 109 154 189 218 243 298 344 385 422 – – 2-1/2" 4.9 7.2 10 12 14 16 18 21 23 26 – –
3" 120 170 240 294 339 379 465 537 600 657 – – 3" 7.6 11 16 19 22 25 29 32 35 41 – –
4" 145 205 290 355 410 459 562 648 725 794 – – 4" 9.2 13 19 23 27 30 35 39 43 49 – –
BYPASS Applications - FULL FLOW thru UPPER Port (Bottom Closed)
Gallons Per Minute Liters per Second
Valve Available Sizing Pressure Differential --- PSI Valve Available Sizing Pressure Differential --- kPa
Size Cv 246810152025304050 Size 7 15 30 45 60 75 100 125 150 200 250 350
1/2" 3.5 4.9 7 8.6 9.9 11 14 16 18 19 22 25 1/2" 0.2 0.3 0.5 0.6 0.7 0.7 0.8 0.9 1 1.2 1.3 1.6
3/4" 6 8.5 12 15 17 19 23 27 30 33 38 42 3/4" 0.4 0.6 0.8 1 1.1 1.2 1.4 1.6 1.8 2 2.3 2.7
1" 11 16 22 27 31 35 43 49 55 60 70 78 1" 0.7 1 1.4 1.8 2 2.3 2.6 3 3.2 3.7 4.2 4.9
1-1/4" 17 24 34 42 48 54 66 76 85 93 108 120 1-1/4" 1.1 1.6 2.2 2.7 3.2 3.5 4.1 4.6 5 5.8 6.5 7.6
1-1/2" 24 34 48 59 68 76 93 107 120 131 152 170 1-1/2" 1.5 2.2 3.2 3.9 4.5 5 5.8 6.4 7.1 8.2 9.1 11
2" 38 54 76 93 107 120 147 170 190 208 240 269 2" 2.4 3.5 5 6.1 7.1 7.9 9.1 10 11 13 14 17
2-1/2" 77 109 154 189 218 243 298 344 385 422 – – 2-1/2" 4.9 7.2 10 12 14 16 18 21 23 26 – –
3" 120 170 240 294 339 379 465 537 600 657 – – 3" 7.6 11 16 19 22 25 29 32 35 41 – –
4" 145 205 290 355 410 459 562 648 725 794 – – 4" 9.2 13 19 23 27 30 35 39 43 49 – –