Product Card
WPS600S
Page - 2 - of 5
www.powerlinkgenset.com
Notes:
1) Ambient reference conditions: 1,000 mbar, 27℃, 30% relative humidity;
2) Standby Power: the maximum power available under varying loads. Only for standby and emergency use. No overload is permissible. Prime
Power: the maximum power available under varying loads for continuous operation. A 10% overload is permissible for 1 hour every 12 hours.
Features Benefits
l Excellent cooling system, reliable operation under harshest
conditions.
l PLC-5220 control panel with AMF function.
l With sound attenuated enclosures available with high
protection against water and dust.
l Designed with safety in mind earth leakage protection.
l Leroy Somer Alternator, IP 23 class ‘H’ insulation.
l Equipped with a ladder (for generators 300-500
kVA ),exterior fueling point,water tank inlet.
l Function stability credibility, service convenience.
l Low operating cost results in optimal economy.
l Gets the job done wherever you are.
l Ease of installation, operation, and maintenance.
Performance Specification and Craftwork
Performance Specification
Telephone Interference, Electromagnetism
Efficiency of Rated Power
96.3%
TIF ≤50
Time needed from start-up to full load
(inductive)
125 seconds
THF ≤2%
Time needed from start-up to 50% load
(inductive) allowed
8 seconds
Radio interference in compliance with BS800 and VED
LEVELS G and N.
1.1 times overload operation time (hour) 1
2.0 time overload operation time (minute)
1
Voltage Regulation, steady state ≤±1%
Voltage Regulation, transient state 20%-15%
Voltage Settle Time ≤5 seconds
Voltage Fluctuation Ratio 0.5%
Frequency Regulation, steady state ±0.5% adjustable
Frequency Regulation, transient state ±5%
Frequency Settle Time 5 seconds
Frequency Fluctuation Ratio 0.5%
Recovery Time 0.5 seconds
Craftwork
● Steel base frame with AV mounting
● standard 8h fuel tank with flexible rubber fuel tube,
fuel level indicator and drainage
● Overall sprayed powder coating
● Whole set documents, including Installation Manual,
Operation Manual, Spare Parts Catalog, Circuit
Diagram
Criterion
● ISO3046, ISO8528, BS4999, BS5514,
● BS5000PT99、AS1359, IEC34
● UTE5100, VDE0530
● ISO9001:2000
3-Phase, 50Hz@1500RPM
Voltage
kW kVA Amps
380 480 600 911.6
400 480 600 866.1
415 480 600 834.7
Prime Power
440 480 600 787.3
380 533.3
666.7 1012.9
400 533.3
666.7 962.3
415 533.3
666.7 927.5
Standby Power
440 533.3
666.7 874.8
Noise Level at 7 meters (dBA) 72.6