WPS300S-AU
50 Hz@1500rpm,3-phase/4-wiring
1 Standards&Conditions
Design Standards
The designs and the productions are in conformity with:
• Conformite Europeenne (CE)
•
• ISO8528-5:2005
• GB/T2820.5-2009
Environmental Operating Conditions
•
Installation place: Outdoors or indoors (well ventilated).
• Ambient temperature: -25℃ to 45℃.The coolant heater
is needed when the temperature is below 5℃
• Humidity: Less than 80%.
• Altitude: Below one thousand (1000) meters.
Factory Inspection
•
Inspection items.
• Protection devices working test.
• Starting ability in normal temperature.
• 50% rated power load moment capability.
• Voltage deviation and speed variation: 0%, 25%, 50%,
75%, 100%, 110% Load.
Painting Process
•
the manufacturer's standard.
• The customer could also choose the color which the
manufacturer offers.
2 General Features
• Perkins engine 1506A-E88TAG5
• Close coupled toaLeroy Somer alternator
LSA46.2VL12
• Microprocessor control module PLC-7420
• ABB main circuit breaker:500A
• Rotate speed governor: Electronic gover- nor
• Excitation system: Self excited , SHUNT
• A.V.R model: R250
• Key switch
• Emergency stop switch
• ATS (automatic transfer switch) receptacle
• 2x12V/120AH sealed for life maintenance free battery
• Lockable battery isolator switch
• Powder coated canopy
• 50℃ radiator
• Oil pump on the engine
• Steel base frame with forkslots
• Vibration isolators between the engine/alternator and
base frame
•
• Base fuel tank for 25 hours running
• Drain points for fuel tank
•
General technical data
Model.......................................................... WPS300S-AU
Structure type .................................................................... R
Tank capacity..............................................................1650L
Dry weight.................................................................4300kg
Noise level @7m ............................................................N/A
Dimensions L×W×H............................ 4100x1600x2400mm
Standby Power ............................................ 330kVA/264kW
Prime Power................................................ 300kVA/240kW
Voltage 380V 400V 415V 440V
Ampere 455.8A 433A 417.3A 417.4A
Genset Fuel Consumption
Frequency/Load 25% 50% 75% 100% 110%
50Hz (L/h) N/A 33 48 65 73