Product Card

WPS1750
Page - 2 - of 5
www.powerlinkgenset.com
Notes
1) Ambient reference conditions: 1,000 mbar, 27, 30% relative humidity;
2) Standby Power: the maximum power available under varying loads. Only for standby and emergency use. No overload is permissible. Prime
Power: the maximum power available under varying loads for continuous operation. A 10% overload is permissible for 1 hour every 12 hours.
Features Benefits
l Excellent cooling system, reliable operation under harshest
conditions.
l PLC-5220 control panel with AMF function.
l Leroy Somer Alternator, IP 23 class H insulation.
l Function stability credibility, service convenience.
l Low operating cost results in optimal economy.
l Gets the job done wherever you are.
l Ease of installation, operation, and maintenance.
Performance Specification and Craftwork
Performance Specification
Telephone Interference, Electromagnetism
Efficiency of Rated Power
96.3%
TIF 50
Time needed from start-up to full load
(inductive)
125 seconds
THF 2%
Time needed from start-up to 50% load
(inductive) allowed
8 seconds
Radio interference in compliance with BS800 and VED
LEVELS G and N.
1.1 times overload operation time (hour) 1
2.0 time overload operation time (minute)
1
Voltage Regulation, steady state ±1%
Voltage Regulation, transient state 20%-15%
Voltage Settle Time 5 seconds
Voltage Fluctuation Ratio 0.5%
Frequency Regulation, steady state ±0.5% adjustable
Frequency Regulation, transient state ±5%
Frequency Settle Time 5 seconds
Frequency Fluctuation Ratio 0.5%
Recovery Time 0.5 seconds
Craftwork
Steel base frame with AV mounting
standard 8h fuel tank with flexible rubber fuel tube,
fuel level indicator and drainage
Overall sprayed powder coating
Whole set documents, including Installation Manual,
Operation Manual, Spare Parts Catalog, Circuit
Diagram
Criterion
ISO3046, ISO8528, BS4999, BS5514,
BS5000PT99AS1359, IEC34
UTE5100, VDE0530
ISO9001:2000
3-Phase, 50Hz@1500RPM
Voltage
kW kVA Amps
380 1400 1750 2658.9
400 1400 1750 2526.0
415 1400 1750 2434.7
Prime Power
440 1400 1750 2296.3
380 1260 1575 2954.4
400 1260 1575 2806.6
415 1260 1575 2705.2
Standby Power
440 1260 1575 2551.5
Noise Level at 7 meters (dBA) 106