Product Card

EC series
GMS30CS-AU
50 Hz@1500rpm,3-phase/5-wiring
1 Standards&Conditions
Design Standards
The designs and the productions are in conformity with:
Conformite Europeenne (CE)
ISO8528-5:2005
GB/T2820.5-2009
AS 3000-1997
AS 3010.1-1988
Environmental Operating Conditions
Installation place: Outdoors or indoors (well ventilated).
Ambient temperature: -25 to 45.The coolant heater
is needed when the temperature is below 5
Humidity: Less than 90%.
Altitude: Below one thousand (1000) meters above sea
level.
Factory Inspection
Inspection items.
Protection devices working test.
Starting ability in normal temperature.
50% rated power load moment capability.
Voltage deviation and speed variation: 0%, 25%, 50%,
75%, 100%, 110% Load.
Painting Process
the manufacturer's standard.
The customer could also choose the color which the
manufacturer offers.
2 General Features
Cummins engine 4B3.9G1
Close coupled toaStamford alternator PI144K
Microprocessor control module PLC-7320
SCHENIDER main circuit breaker: 3-Phase 63A
Rotate speed governor: Mechanical governor
Excitation System: Self ExcitedSHUNT
A.V.R.Model: AS480
Key switch
Emergency stop switch
ATS (automatic transfer switch) receptacle
Remote run connextor
2x12V sealed for life maintenance free battery
Lockable battery isolator switch
Powder coated canopy
50 radiator
Oil pump on the engine
Non-returning valve for fuel inlet hose of the engine
Steel base frame with forkslots
Vibration isolators between the engine/alternator and
base frame
Base fuel tank for 40 hours running
Drain points for fuel tank
Breather valve for fuel tank
General technical data
Model............................................................ GMS30CS-AU
Structure type .................................................................... R
Tank capacity................................................................270L
Dry weight..............................................................1398.2kg
Noise level @7m ............................................................N/A
Dimensions L×W×H............................ 2588x1101x1708mm
Standby Power ................................................ 32kVA/26kW
Prime Power.................................................... 30kVA/24kW
Voltage
380V 400V 415V 440V
Ampere 45.6A 43.3A 41.7A 39.4A
Genset Fuel Consumption
Frequency/Load 25% 50% 75% 100% 110%
50Hz (L/h) 1.6 3.2 4.8 6.4 7.0