Machine Component Identification
14
Liquid Crystal
Display (LCD)
Screen
The main section of the LCD screen 2 shows the operating status of the
generator. Pushing the Operation key 3 will toggle through the status of (V)
volts, (A) amps, (VA) volt amps/watts and (Hour) current run time and
accumulated run time. In addition, the following symbols will display
across the top of the LCD screen when a failure occurs or maintenance time
is indicated.
Over voltage occurs when the AC voltage is > greater than 133V and DC
voltage is > greater than 275V for more than 1 second.
Under voltage occurs when the AC voltage is < less than 108V and DC
voltage is < less than 36V for more than 5 seconds.
Output over current occurs when the Amps are > greater than 1.2 the
rated Amps.
Output short circuit occurs when an abnormal problem is encountered
with electrical power. The short circuit protection happens within 4 seconds
to protect the generator and stop further damage.
Over heat condition occurs when the internal temperature of the inverter is
higher than 285 degrees Fahrenheit (285°F). Check for adequate air flow
and any blockages.
Maintenance time is displayed when the generator reaches 200 hours of
running time. It cannot be reset.
Output short circuit
Over heat
Over voltage
Under voltage
Output over current
Maintenance time