Product Manual
Installation / Initial Set-Up 
25 
5. Grounding the Generator 
Always ensure the generator is properly grounded to prevent electrical shock. 
You must always ground the generator by the following method when using the generator as a 
portable electrical source: 
1) Drive a 3/4" or 1" copper pipe or rod into the ground close to the generator. The pipe/rod 
must penetrate moist earth – the depth required will be dictated by local soil conditions. 
Consult with an electrician. 
2) Connect an approved ground clamp to the pipe. 
3) Run a 10 or 8 gauge wire from the clamp to the generator grounding post located on the 
electrical panel. 
4) Do not connect the generator grounding post to a water pipe or a ground used by a radio 
system. 
If a licensed electrician installs the generator with a connection to your building’s electrical circuit 
for use as a back-up power system, grounding may alternatively be completed through the 
building’s grounding system. Ask your electrician. If the generator is not grounded through your 
building’s electrical system, follow the procedure above. 
 WARNING: 
Operating the generator when it is not properly grounded can result in electrical shock. 
Copper 
Pipe/Rod 
Grounding Post 
Ground 
10 or 8 Ga. Wire 