Product Manual
10
Scroll Air Compressors Tankmount/Basemount
Figure 9 - 3-5 HP Duplex Single-Phase 208-230 Volts
NOTES:
1. RECOMMENDED TIGHTENING TORQUES FOR WIRE TERMINALS:
208-460 VOLT POWER 35 POUND INCHES
115 VOLT POWER, CONTROL
AND LOW VOLTAGE 20 POUND INCHES
2. PANEL GROUND MUST BE CONNECTED TO EARTH GROUND
3. INSTALLER TO PROVIDE MAIN DISCONNECTING DEVICE WITH
SHORT CIRCUIT PROTECTION FOR THIS ELECTRICAL ASSEMBLY.
SEE TABLE 1 FOR SIZING INFORMATION.
4. ALL WIRES MUST BE LABELED ON BOTH ENDS
5. TRANSFORMER IS SIZED FOR LOADS SHOWN ON DRAWING
ONLY. DO NOT CONNECT ANY OTHER DEVICES
VOLTAGE WIRE NUMBERS GAUGE COLOR
120 V AC 001-699 16 - 18 AWG RED/BLK
0 V AC W 16 - 18 AWG WHT/BLK
24 V DC 700-999 16 - 18 AWG
PURPLE0 V DC 701 16 - 18 AWG
PURPLE
GND - VARIES GREEN
CUSTOMER 01-99 YELLOW
SUPPLY
WIRE TYPE TABLE
16 AWG