Owner's Manual

MFG# 5401175 - REV E
1/16
PRINTED IN USA PAGE 2 OF 2
RA-4410RC
REMOTE ANNUNCIATOR
ANNUNCIATOR SELECTOR
SWITCH SET FOR THE TOTAL
NUMBER OF DEVICES INST
ALLED
ON THE RS-485 TERMINALS
REMOVE THE RESISTOR FROM
THE PFC-4410RC AND INSTALL
ON THE LAST DEVICE ONLY.
120 OHM RESISTOR -
CONNECT THE DRAIN WIRE OF THE SHIELDED
CABLE TO THE S TERMINAL ON THE PFC-4410RC
ONLY. DO NOT CONNECT THE DRAIN WIRE TO ANY
ANNUNCIATOR. THE DRAIN WIRE MUST MAKE A
CONTINUOUS PATH TO THE LAST ANNUNCIATOR
WHERE IT IS CUT OFF AND INSULATED.
ANNUNCIATOR ADDRESS SWITCH (FIRST DEVICE, ADDRESS 1)
DO NOT CONNECT THE SHIELDED CABLE TO
THE REMOTE ANNUNCIATOR
INSTALL THE RESISTOR ON THE LAST RA-4410RC ONLY
ANNUNCIATOR ADDRESS SWITCH
DWG# 1175-2
24 VDC
RS-485
S
24 VDC
RS-485
S
S
RS-485
24 VDC
DO NOT CONNECT THE SHIELDED CABLE TO
THE REMOTE ANNUNCIATOR
CUT OFF AND ISOLATE THE DRAIN WIRE AT THE LAST
DEVICE. DO NOT CONNECT THE DRAIN WIRE TO ANY
DEVICE.
PFC-4410RC Main Board
RA-4410RC #1
RA-4410RC #2
DO NOT CONNECT THE SHIELDED CABLE TO THE
REMOTE ANNUNCIATOR
DO NOT CONNECT THE SHIELDED CABLE TO THE
REMOTE ANNUNCIATOR